Plan Review Notes
Plan Review Notes For Project Z16070018
Project Number Z16070018
Review Stop STORM
Sequence Number 2
Notes
Date Text
2016-12-05 11:05:44COMMENTS FROM THE REVIEW OF THE 11/18/2016 RESUBMITTAL.
  
 1. EXISTING PARKING LOT IS BEING MODFIED / EXPANDED.
 ADD WATER QUALITY TREATMENT FOR THIS PARKING LOT
 2. REVIEW GRADING PLAN AND PROVIDE FLOW ARROWS
 INDICATING DIRECTION OF FLOW OF SURFACE RUNOFF. IT IS
 NOT CLEAR WHERE THE RUNOFF FROM THE PARKING SPACES NEXT
 TO THE BUILDING WILL END UP.
 3. SIDEWALK AND CURBING IN RIGHT-OF-WAY TO BE
 CONSTRUCTED PER CITY STANDARD DETAILS. TYPE ?F? CURB TO
 BE CONSTRUCTED IN THE RIGHT-OF-WAY. DROP CURB ALONG THE
 DRIVEWAY IF NEEDED.
 4. DRIVEWAY APRON TO BE CONSTRUCTED PER CITY STANDARD
 DETAILS.
 5. SHOW CONCRETE SIDEWALK ACROSS DRIVEWAY.
 6. EXISTING INLET AT NORTH CORNER OF THE EXISTING
 BUILDING TO BE CONVERTED TO MANHOLE TOP.
  