| 2016-08-08 09:57:10 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM |
| | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE |
| | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE |
| | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH |
| | THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, |
| | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. |
| | |
| | THIS APPEARS TO BE AN ASSEMBLY OCCUPANCY SPACE AND |
| | SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS. A REVIEW |
| | OF THE PROPOSED EXIT STAIRS WIDTH MAY BE NECESSARY TO |
| | ENSURE IT MEETS THE OCCUPANCY EXIT REQUIREMENTS. |
| | |
| | 6. BASED ON SOME OF THE DESIGN PICTURES AND VARYING |
| | OVERHEAD ROOFING/CANOPIES AND A POTENTIAL OCCUPANCY |
| | OVER 300 A FIRE SPRINKLER AND FIRE ALARM MAY BE |
| | REQUIRED. |
| | |
| | ANY EXISITNG ENGINEERED FIRE AND LIFE SAFETY SYSTEM(S) |
| | IN THE MAIN STRUCTURE(S) SHALL BE EXTENDED INTO THE |
| | PROPOSED PROJECT TO PROVIDE THE SAME OR EQUAL LEVEL OF |
| | FIRE AND LIFE SAFETY. |
| | |
| | 7. ANY PROPOSED CANOPY CONFIGURATION SHALL BE OF A |
| | LISTED FIRE RETARDANT/PROOF CONSTRUCTION MATERIAL. |
| | |
| | 8. OPEN FLAME(S) EFFECTS/DEVICES ARE PROHIBITED UNLESS |
| | SPECIFACCALY APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL. |
| | |
| | 9. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES |
| | NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| | |
| | 10. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| |