| 2016-07-13 15:37:56 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. ACCESSIBLE PARKING SPACE DISTRIBUTION. SHEET A-G, |
| | GARAGE PLAN, SHOWS ONLY ONE ACCESSIBLE PARKING SPACE |
| | ADJACENT TO THE ELEVATORS SERVING THE SOUTH RESIDENTIAL |
| | BUILDING, AND IT SHOW NO ACCESSIBLE SPACES NEAR THE |
| | ELEVATORS SERVING THE RESIDENTIAL UNITS AT THE EAST END |
| | OF THE MAIN BUILDING. PER SECTION 208.3 OF FLORIDA |
| | ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES ARE TO BE |
| | LOCATED ON THE SHORTEST POSSIBLE ROUTE OF TRAVEL FROM |
| | ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE FOR EACH |
| | BUILDING. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL |
| | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE |
| | |
| | 3. VAN ACCESSIBLE PARKING SPACES. NONE OF THE PROPOSED |
| | ACCESSIBLE PARKING SPACES ARE NOTED AS VAN ACCESSIBLE. |
| | PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE |
| | IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A |
| | PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND |
| | DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA |
| | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 |
| | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 4. CONSTRUCTION TYPE. WHEN SUBMITTED FOR BUILDING |
| | PERMIT, THE PLANS SHALL SHOW THAT THE TYPE OF |
| | CONSTRUCTION FOR THE BUILDINGS WILL BE IN ACCORDANCE |
| | WITH THE HEIGHT, AREA AND OCCUPANCY LIMITATIONS IN |
| | CHAPTER 5 OF THE FLORIDA BUILDING CODE |
| | |
| | 5. HORIZONTAL SEPARATION. WHEN SUBMITTED FOR BUILDING |
| | PERMIT, COMPLIANCE WITH ALL BUILDING SEPARATION, |
| | PERCENTAGE OF OPENINGS AND OPENING PROTECTIVE |
| | REQUIREMENTS OF CHAPTERS 6 AND 7 OF THE FLORIDA |
| | BUILDING CODE SHALL BE VERIFIED. |
| | |
| | 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 8. BUILDING ADDRESSES. EACH SEPARATE BUILDING SHALL |
| | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT |
| | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 |
| | 1080, OR BY EMAIL: [email protected] |
| | |
| | 9. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT |
| | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE |
| | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP |
| | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC |
| | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | 10. THE PROPERTY LINE THAT SEPARATES THE PROPOSED EL |
| | FLAMINGO PROJECT FROM THE SINGLE FAMILY RESIDENCE LOT |
| | TO THE EAST SHALL EITHER BE MOVED, SO THAT THE EL |
| | FLAMINGO PARKING GARAGE ACCESS RAMP DOE NOT CROSS THE |
| | PROPERTY LINE, OR A UNITY OF TITLE OTHER LEGAL |
| | INSTRUMENT SHALL BE PROVIDED TO DEMONSTRATE CONTROL |
| | OVER FUTURE DEVELOPMENT AND USE OF THE SINGLE FAMILY |
| | RESIDENCE LOT. |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |