2016-07-12 18:31:41THIS IS A PRELIMINARY REVIEW OF THE CONCEPTUAL PAVING,
 DRAINANGE, WATER AND WASTEWATER PLAN. ADDITIONAL
 COMMENTS ARE EXPECTED WHEN FULL DRAWINGS ARE SUBMITTED
 FOR ENGINEERING DEVELOPMENT APPROVAL APPLICATION:
  
 1. PLEASE PROVIDE THE ESTIMATED WATER AND SEWER DEMANDS
 (AVERAGE AND PEAK) AND FIRE FLOW DEMAND;
 2. CITY'S RECORD INFORMATION INDICATES THAT THE
 EXISTING WM ON BARCELONA ROAD IS 20-INCH TRANSITE/AC AT
 THE PROPOSED FIRE SERVICE LINE CONNECTION. CONSIDER
 EXTENDING A 12-INCH WM FROM S. DIXIE HWY FROM A 12-INCH
 WM STUB OUT TO THE PROPOSED CONNECTION. PLEASE PROVIDE
 PROFILE OF THE PROPOSED WM WITHIN THE ROADWAY R/W FROM
 THE POINT OF CONNECTION TO THE POINT OF SERVICE;
 3. CITY'S RECORD INFORMATION INDICATES THAT THERE IS AN
 EXISTING 3-INCH TRANSITE/AC WM RUNNING EAST-WEST FROM
 S. DIXIE TO OLIVE AVENUE BETWEEN BARCELONA ROAD AND
 CORDOVA ROAD. THIS WM WILL BE UNDER THE PROPOSED
 BUILDING (RETAIL/RESIDENTIAL/GARAGE) BETWEEN BARCELONA
 AND CORDOVA. PLEASE ADDRESS.
 4. THE CITY WILL VERIFY THAT THE EXISTING 8-INCH
 SANITARY SEWER IN THE EAST-WEST CORRIDOR BETWEEN
 FLAMINGO DRIVE AND BARCELONA ROAD ON THE DEVELOPMENT
 SITE IS PRIVATE.
 5. EXISTING UTILITY SERVICE LINES (WATER AND SEWER), IF
 NOT USED BY THE SITE REDEVELOPMENT, ARE TO BE CUT AND
 CAPPED AT THE MAIN AND REMOVED IF LARGER THAN 2 INCHES
 IN DIAMETER. PLEASE ADD THE APPROPRIATE NOTES ON THE
 WATER & WASTEWATER PLAN;
 6 PLEASE PROVIDE CCTV RECORD (VIDEO AND TV LOG) OF THE
 EXISTING SAN SEWER MAIN ON S. DIXIE HWY TO DETERMINE
 THE LOCATION OF EXISTING SANITARY SEWER LATERALS;
 7. PLEASE PROVIDE THE FIRE HYDRANT FLOW TEST DATA FROM
 EXISTING FIRE HYDRANT USED FOR DESIGN;
 8. PLEASE SHOW EXISTING WATER AND SEWER SYSTEM
 INCLUDING PIPE SIZE, MATERIAL, CONNECTIVITY, AND
 VALVING. CONTACT ENGINEERING DEPARTMENT @ 561-494-1040
 FOR SYSTEM INFORMATION. ALL INFORMATION IS TO BE FIELD
 VERIFIED BY THE DESIGN ENGINEER.
 9. PLEASE INCLUDE APPLICABLE CITY OF WEST PALM BEACH
 STANDARD WATER AND SEWER DETAILS TO THE DETAILS SHEET.
 CONTACT THE ENGINEERING SERVICES DEPARTMENT (561)
 494-1040 FOR THE LATEST REVISED DETAILS.
  
 LAURA LE, P.E.
 PUBLIC UTILITIES ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, FOURTH FLOOR
 WEST PALM BEACH, FLORIDA 33401
 561-494-1040
 [email protected]
  