2016-07-12 17:14:24THIS IS A PRELIMINARY REVIEW OF THE CONCEPTUAL CIVIL
 PLAN. ADDITIONAL COMMENTS ARE EXPECTED WHEN DRAWINGS
 ARE SUBMITTED FOR ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION.
 1. THE CITY IS REVIEWING THE EXISTING WATER AND SEWER
 MAINS AND CONNECTIONS (LOCATION, ALIGNMENT, PIPE SIZE,
 VALVES, FIRE HYDRANT, ETC) AS CURRENTLY DEPICTED ON
 SHEET C-3
 2. PLEASE CHANGE WATER MAIN PIPE DIAMETER FROM 16 FT
 TO16 INCHES, SANITARY SEWER FROM 8 FT TO 8 INCHES, AND
 FORCE MAIN FROM 24 FT TO 24 INCHES
 3. PLEASE ADD THE EXISTING WATER METER AND METER
 BOX/VAULT AND CALL OUT THE METER SIZE
 4. PLEASE PROVIDE CALCULATIONS FOR THE INCREASED WATER
 DEMAND (AVERAGE AND PEAK) AND DEMONSTRATE THAT THE
 EXISTING METER SIZE IS ADEQUATE FOR THE ADDITIONAL
 DEMAND
  
 LAURA LE, PE
 PUBLIC UTILITIES ENGINEER