Plan Review Notes
Plan Review Notes For Project Z16060058
Project Number Z16060058
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2017-01-13 15:45:26CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
  
 PROJECT NAME: 2101 N. AUSTRALIAN AVE. ? JOSEPH?S
 VILLAGE - Z16060058
 DATE: JANUARY 13, 2017
  
 STATUS: PASSED WITH PROVISO (STATED BELOW):
  
 AFTER A REVIEWING THE REVISED PLANS IT APPEARS THAT
 SOME OF THE PREVIOUS COMMENTS FOR CIVIL PLAN HAVE BEEN
 ADDRESSED. HOWEVER, COMMENTS MADE BY CITY?S PUBLIC
 UTILITIES ENGINEER (MADE ON 07/12/2016, FOR JULY PPRC),
 ARE STILL APPLICABLE AND ARE ADDED TO THE NEW COMMENTS.
 ALL THESE COMMENTS ARE EXPECTED TO BE ADDRESSED DURING
 ?ENGINEERING DEVELOPMENT APPLICATION? PHASE PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL:
  
 A) GENERAL COMMENT:
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC
 WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION FORMS CAN BE DOWNLOADED AT:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 2. PLEASE SUBMIT THE LATEST VERSION OF THE ?AUTO-CALC
 CERTIFIED COST ESTIMATE FORM? FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT. THIS FORM CAN
 BE DOWNLOADED FROM THE FOLLOWING LINK:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 3. SOLID WASTE YARDAGE CALCULATION WILL NEED TO BE
 SUBMITTED AS PART OF THE FINAL DESIGN TO VERIFY THAT
 THE DESIGN INCLUDES APPROPRIATE NUMBER AND SIZE OF
 DUMPSTERS/GARBAGE RECEPTACLES. PLEASE SHOW ON THE PLAN
 IF A COMPACTOR IS PROPOSED TO REDUCE THE YARDAGE OF
 WASTE THAT WILL NEED TO BE COLLECTED;
  
 4. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING
 THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS THE
 PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. THE TRASH
 DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY
 SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER
 PER SECTION 74-35(A)(5) OF THE CODE OF ORDINANCES. IF A
 ROLL?OFF COMPACTOR IS PROPOSED, PLEASE PROVIDE A LETTER
 FROM THE PRIVATE PROVIDER VERIFYING THAT THEY CAN
 PROVIDE SERVICE WITH THE CONFIGURATION SHOWN ON THE
 PLANS;
  
 B) UTILITY COMMENTS:
  
 5. THE CITY IS REVIEWING THE EXISTING WATER AND SEWER
 MAINS AND CONNECTIONS (LOCATION, ALIGNMENT, PIPE SIZE,
 VALVES, FIRE HYDRANT, ETC.) AS CURRENTLY DEPICTED ON
 SHEET C?3;
  
 6. PLEASE ADD THE EXISTING WATER METER AND METER
 BOX/VAULT AND CALL OUT THE METER SIZE
  
 7. PLEASE PROVIDE CALCULATIONS FOR THE INCREASED WATER
 DEMAND (AVERAGE AND PEAK) AND DEMONSTRATE THAT THE
 EXISTING METER SIZE IS ADEQUATE FOR THE ADDITIONAL
 DEMAND.
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1124 (OFFICE)
  