Plan Review Notes
Plan Review Notes For Project Z16040006
Project Number Z16040006
Review Stop PU
Sequence Number 1
Notes
Date Text
2016-07-08 01:18:48THIS IS A PRELIMINARY REVIEW OF THE UTILITY PLAN.
 ADDITIONAL COMMENTS ARE EXPECTED WHEN DRAWINGS ARE
 SUBMITTED FOR ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION.
  
 1. PLEASE PROVIDE FIRE DEMAND
 2. PLEASE LABEL PRIVATE FIRE HYDRANT AS "PRIVATE FIRE
 HYDRANT" AND CALL OUT THE POINT OF SERVICE
 3. CCTV RECORD OF THE EXISTING 8"VCP SANITARY SEWER
 MAIN INDICATES THAT THERE IS AN EXISTING SERVICE
 LATERAL SERVING THE PROPERTY. THIS SERVICE IS LOCATED
 AT APPROX. 25 FEET SOUTH OF THE NORTH PROPERTY (UNDER
 THE PROPOSED DRIVEWAY). EXISTING UTILITY SERVICE LINES,
 IF NOT UTILIZED BY THE DEVELOPMENT, ARE TO BE CAPPED AT
 THE MAIN AND REMOVED. PLEASE ADD THE APPROPRIATE NOTES
 TO THE UTILITY PLAN.
 4. PLEASE INCLUDE APPLICABLE CITY'S STANDARD WATER AND
 SEWER DETAILS ON THE CONSTRUCTION DETAILS PLAN SHEET -
 FIRE HYDRANT, PIPE RESTRAINT TABLE, ETC. CONTACT THE
 ENGINEERING DEPARTMENT AT 561-494-1040 FOR THE LATEST
 REVISED DETAILS.
  
2016-05-10 15:42:38SEE COMMENTS UNDER ENG PPRC