| Plan Review Notes For Project Z16040006 |
| Project Number |
Z16040006 |
|
| Review Stop |
PU |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-08 01:18:48 | THIS IS A PRELIMINARY REVIEW OF THE UTILITY PLAN. | | | ADDITIONAL COMMENTS ARE EXPECTED WHEN DRAWINGS ARE | | | SUBMITTED FOR ENGINEERING DEVELOPMENT APPROVAL | | | APPLICATION. | | | | | | 1. PLEASE PROVIDE FIRE DEMAND | | | 2. PLEASE LABEL PRIVATE FIRE HYDRANT AS "PRIVATE FIRE | | | HYDRANT" AND CALL OUT THE POINT OF SERVICE | | | 3. CCTV RECORD OF THE EXISTING 8"VCP SANITARY SEWER | | | MAIN INDICATES THAT THERE IS AN EXISTING SERVICE | | | LATERAL SERVING THE PROPERTY. THIS SERVICE IS LOCATED | | | AT APPROX. 25 FEET SOUTH OF THE NORTH PROPERTY (UNDER | | | THE PROPOSED DRIVEWAY). EXISTING UTILITY SERVICE LINES, | | | IF NOT UTILIZED BY THE DEVELOPMENT, ARE TO BE CAPPED AT | | | THE MAIN AND REMOVED. PLEASE ADD THE APPROPRIATE NOTES | | | TO THE UTILITY PLAN. | | | 4. PLEASE INCLUDE APPLICABLE CITY'S STANDARD WATER AND | | | SEWER DETAILS ON THE CONSTRUCTION DETAILS PLAN SHEET - | | | FIRE HYDRANT, PIPE RESTRAINT TABLE, ETC. CONTACT THE | | | ENGINEERING DEPARTMENT AT 561-494-1040 FOR THE LATEST | | | REVISED DETAILS. | | | | | 2016-05-10 15:42:38 | SEE COMMENTS UNDER ENG PPRC |
| |