| Plan Review Notes For Project Z16020017 |
| Project Number |
Z16020017 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-08-18 13:40:50 | 3RD REVIEW RESPONSE | | | | | | THERE WERE NO NOTES, NARRATIVES OR CLOUD REVISION | | | INDICATING COMPLIANCE OR ACKNOWLEDGEMENT OF THE | | | PREVIOUSLY SUBMITTED FIRE PREVENTION BUREAU COMMENTS. | | | | | | HOWEVER, THIS PROJECT APPEARS TO MEET THE DEFINITION OF | | | A HIGH RISE PER THE FLORIDA FIRE PREVENTION CODE, 5 | | | EDITION AND THE BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED. | | | | | | THE CONCEPTUAL ENGINEERING PLAN INDICATES A SINGLE | | | WATER SUPPLY FOR THE FIRE PROTECTION SYSTEM, TWO ARE | | | REQUIRED. A DOUBLE CHECK FOR THE FIRE LINE IS NOT | | | INDICATED. IT SHALL INSTALLED IN ACCORDANCE WITH NFPA | | | 24 AND BE A MINIMUM 40' FROM THE BUILDING OR CONTAINED | | | WITHIN A 2 HOOUR ENCLOSURE. PLEASE COORDINATE THESE | | | ITEMS THROUGH THE OFFICE OF THE FIRE MARSHAL. | | | | | | THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES | | | NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT | | | THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE LIFE SAFETY CODES AND | | | STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | [email protected] |
| |