| Plan Review Notes For Project Z16020016 |
| Project Number |
Z16020016 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-08-18 14:35:15 | 3RD REVIEW RESPONSE | | | | | | THERE WERE NO NOTES, NARRATIVES, OR CLOUD REVISIONS | | | INDICATING COMPLIANCE OF ACKNOWLEDGEMENT THE PREVIOUSLY | | | SUBMITTED FIRE PREVENTION BUREAU COMMENTS. HOWEVER, THE | | | BUREAU HAS NO OBJECTIONS TO THE PROJECTAND. | | | | | | A DOUBLE CHECK VALVE BACK FLOW PREVENTER FOR THE FIRE | | | LINE IS NOT INDICATED ON THE CONCEPTUAL ENGEERING PLAN. | | | PER NFPA 24 THIS BACK FLOW PREVENTER SHALL BE LOCATED | | | 40' FROM THE BUILDING OR WITHIN A 2 HOUR ENCLOSURE. | | | PLEASE COORDINATE THE LOCATION THROUGH THE OFFICE OF | | | THE FIRE MARSHAL. | | | | | | THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES | | | NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT | | | THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE LIFE SAFETY CODES AND | | | STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
| |