Plan Review Notes For Project Z16020016
Project Number Z16020016
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2017-08-18 14:35:153RD REVIEW RESPONSE
  
 THERE WERE NO NOTES, NARRATIVES, OR CLOUD REVISIONS
 INDICATING COMPLIANCE OF ACKNOWLEDGEMENT THE PREVIOUSLY
 SUBMITTED FIRE PREVENTION BUREAU COMMENTS. HOWEVER, THE
 BUREAU HAS NO OBJECTIONS TO THE PROJECTAND.
  
 A DOUBLE CHECK VALVE BACK FLOW PREVENTER FOR THE FIRE
 LINE IS NOT INDICATED ON THE CONCEPTUAL ENGEERING PLAN.
 PER NFPA 24 THIS BACK FLOW PREVENTER SHALL BE LOCATED
 40' FROM THE BUILDING OR WITHIN A 2 HOUR ENCLOSURE.
 PLEASE COORDINATE THE LOCATION THROUGH THE OFFICE OF
 THE FIRE MARSHAL.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE LIFE SAFETY CODES AND
 STANDARDS.
  
  