| 2016-03-08 15:54:13 | 1. PROPOSED PROJECT DOES NOT COMPLY WITH CURRENT |
| | COMPREHENSIVE PLAN AND ZLRDRS. A CODE AMENDMENT WILL BE |
| | NECESSARY TO ALLOW A 7-STORY BUILDING ON THE SITE. |
| | - ICD-5 HAS A MAXIMUM HEIGHT OF 5-STORIES. PROPOSED |
| | BUILDING EXCEED HEIGHT PERMITTED. |
| | 2. A PORTE COCHERE IS NOT PERMITTED ALONG A SECONDARY |
| | STREET SUCH AS RAILROAD AVENUE WITHIN ICD . |
| | 3. SIDEWALK AROUND THE ENTIRE PROJECT IS RECOMMENDED TO |
| | BE AT LEAST 12 FEET. |
| | 4. FURTHER DISCUSSION IS NECESSARY TO DETERMINE THE |
| | DESIRABLE SECTION FOR THE PROPOSED 4TH STREET. STAFF |
| | RECOMMENDS 11? TRAVEL LANES, AND 8? ON-STREET PARKING |
| | (COUNTING THE GUTTER). |
| | 5. PLEASE INDICATE THE ALIGNMENT OF THE PROPOSED 4TH |
| | STREET IN RELATION TO THE EXISTING 4TH STREET WEST OF |
| | ROSEMARY AVENUE. |
| | 6. PRIVATE OPEN SPACE DOES NOT PROVIDE MINIMUM AMOUNT |
| | REQUIRED BY CURRENT CODE. |
| | 7. STREET TREES SHALL BE PLANTED ALONG 3RD STREET ON |
| | TREE GRATES ADJACENT TO THE CURB (30? SEPARATION). |
| | 8. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE |
| | WITH THE BLANK WALL REGULATION. |
| | 9. TREE GRATES SHALL BE 4? BY 4?. |
| | 10. PLEASE INDICATE THE PARKING RAMP PROPOSED SLOPE |
| | (SEC 94-111 (Q)(2) ? NON-PARKING RAMP SLOPE HIGHER THAN |
| | 14% REQUIRES A BREAK-OVER TRANSITION). |
| | 11. ALL DRIVEWAY SHALL BE MAINTAINED AT THE ADJACENT |
| | SIDEWALK LEVEL. |
| | 12. PLEASE INDICATE HOW IS THE GARBAGE PICK-UP |
| | OPERATION (CIRCULATION, STAGING, PRIVATE OR PUBLIC). |
| | PLEASE PROVIDE AUTO TURN FOR THE LOADING AREAS. |
| | 13. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE |
| | WITH PLANAR BREAK REGULATIONS. |
| | 14. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE |
| | WITH TRANSPARENCY REGULATIONS. |
| | |
| | ADDITIONAL COMMENTS: |
| | 15. SURVEY SHALL INCLUDE MEASUREMENTS OF THE EXISTING |
| | SIDEWALKS, AND ROW INCLUDING SIDEWALK ACROSS THE STREET |
| | UP TO THE FACE OF BUILDINGS. |
| | 16. PLEASE ADJUST THE SITE SQUARE FOOTAGE TO REFLECT |
| | THE SURVEY INFORMATION (1.18 AC= 51,401 SF= MAX DEV |
| | CAPACITY OF 141,352 SF) |
| | 17. THE SITE PLAN DRAWING SHALL INCLUDE THE ADJACENT |
| | BUILDINGS AND STREET, INCLUDING THE BUILDINGS ACROSS |
| | THE STREET , AND SHOW THE PROJECT INSERTED IN THE |
| | CONTEXT. |
| | 18. PLEASE PROVIDE ELECTRONIC DRAWINGS (DXF OR CADD) TO |
| | ALLOW THE MEASUREMENT OF THE FAR AREA INDICATED IN |
| | SHEET A0.06. |
| | 19. PLEASE INCLUDE PROPERTY LINES AND SETBACK LINES IN |
| | ALL FLOOR PLANS AND ELEVATIONS. |
| | 20. COLORED ELEVATIONS (ALL FACADES) SHALL INCLUDE CALL |
| | OUT MATERIALS AND REFERENCE PICTURES OF PROPOSED |
| | MATERIALS (INDICATE SCALE). FACADES SHALL INCLUDE |
| | ADJACENT BUILDINGS (INCLUDING ACROSS THE STREET) TO |
| | SHOW THE PROJECT IN ITS CONTEXT. |
| |