| 2016-03-09 10:16:22 | CITY OF WEST PALM BEACH |
| | PUBLIC WORKS DEPARTMENT |
| | |
| | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL |
| | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION |
| | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE |
| | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT |
| | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT |
| | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT |
| | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ |
| | |
| | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE |
| | PLAN APPROVAL. |
| | |
| | 1. PLEASE SUBMIT ESTIMATES FOR THE PEAK POTABLE WATER |
| | DEMAND, SANITARY SEWER FLOW, AND SOLID WASTE COLLECTION |
| | YARDAGE. |
| | |
| | 2. A MAINTENANCE AGREEMENT WILL BE REQUIRED FOR THE |
| | NON-STANDARD ELEMENTS (TREES AND TREE GRATES; PAVERS, |
| | ETC.) PROPOSED WITHIN CITY RIGHT-OF-WAY. |
| | |
| | 3. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING |
| | THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS THE |
| | PROPOSED DUMPSTER/COMPACTOR LOCATIONS. THE TRASH |
| | DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY |
| | SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER |
| | PER SECTION 74-35(A)(5) OF THE CODE OF ORDINANCES. IF A |
| | ROLL-OFF COMPACTOR IS PROPOSED, PLEASE PROVIDE A LETTER |
| | FROM THE PRIVATE PROVIDER VERIFYING THAT THEY CAN |
| | PROVIDE SERVICE WITH THE CONFIGURATION SHOWN ON THE |
| | PLANS. |
| | |
| | 4. DETAILS SHEETS WILL NEED TO UTILIZE STANDARD CITY OF |
| | WEST PALM BEACH DETAILS, WHICH MAY BE DOWNLOADED AT |
| | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ |
| | |
| | 5. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE |
| | AVAILABLE AT HTTP://WWW.CO.PALM-BEACH.FL.US/NEWSROOM/08 |
| | 14/08-26-14-FLOOD_MAPS.HTM. PLEASE REVIEW THE MAPS AND |
| | VERIFY THAT THE NEW MAPS WILL NOT IMPACT THE PROPOSED |
| | PROJECT. |
| | |
| | 6. PLEASE SHOW THE SIGHT TRIANGLES ON THE GROUND FLOOR |
| | LANDSCAPING PLAN FOR THE INTERSECTIONS AND VEHICULAR |
| | EXITS. (SECTION 94-305E, CODE OF ORDINANCES) |
| | |
| | 7. A TRAFFIC STUDY WILL BE REQUIRED FOR THIS PROJECT |
| | SHOWING HOW THE PROPOSED DEVELOPMENT WILL AFFECT THE |
| | TRAFFIC VOLUME AND SURROUNDING LOCAL ROADWAYS. INCLUDE |
| | TRAFFIC ACCIDENT DATA FOR AFFECTED STREET CORRIDORS. |
| | ESTIMATE INCREASED OR DECREASED POTENTIAL. SAFETY |
| | IMPROVEMENTS SHALL BE RECOMMENDED WHERE NECESSARY. |
| | PLEASE SCHEDULE A MEETING WITH THE CITY TRAFFIC |
| | ENGINEER (BRIAN COLLINS) TO DETERMINE THE SCOPE OF THE |
| | REQUIRED STUDY. |
| | |
| | 8. PLEASE REVISE THE LANDSCAPE PLAN TO SHOW LOCATIONS |
| | OF ALL WATER METERS, VALVES, CLEAN-OUTS, LIGHT POLES, |
| | ETC. ROOT BARRIERS MAY BE REQUIRED WHERE PLANTINGS ARE |
| | NEAR UNDERGROUND STORMWATER, SANITARY, OR POTABLE WATER |
| | LINES. |
| | |
| | 9. THE AVAILABLE WATER PRESSURE IN THIS PORTION OF THE |
| | CITY MAY NOT BE ACCEPTABLE AT ELEVATIONS HIGHER THAN |
| | THE 2ND FLOOR. WE RECOMMEND A LONG-TERM PRESSURE STUDY |
| | BE PERFORMED PRIOR TO FINALIZATION OF THE UTILITY |
| | DESIGN. |
| | |
| | 10. PLEASE COORDINATE WITH THE CITY PUBLIC UTILITIES |
| | ENGINEER (LAURA LE) FOR THE PROPOSED UTILITY TIE IN |
| | LOCATIONS. THE AGE AND CONDITION OF THE EXISTING PIPES |
| | MAY NOT BE ADEQUATE FOR THE PROPOSED CONNECTIONS. THE |
| | SUBMITTED DRAWINGS ARE NOT CONSISTENT WITH PREVIOUS |
| | DISCUSSIONS WITH CITY STAFF. |
| | |
| | 11. PLEASE SHOW THE LOCATIONS OF ROOF DRAINS AND |
| | INDICATE WHERE THE DISCHARGE WILL BE DIRECTED. RUNOFF |
| | VELOCITY AND VOLUME SHOULD NOT EXCEED EXISTING |
| | CONDITIONS. |
| | |
| | 12. INDICATE MILLING AND RESURFACING LIMITS AROUND |
| | TRENCH CUTS ON CITY STREETS. |
| | |
| | 13. EACH BUILDING SHOULD HAVE ITS PROPORTIONATE SHARE |
| | OF STORM WATER TREATMENT AND PEAK FLOW ATTENUATION. |
| | PLEASE ALSO SHOW THE LOCATIONS OF ROOF DRAINS AND |
| | INDICATE WHERE THE DISCHARGE WILL BE DIRECTED. RUNOFF |
| | VELOCITY AND VOLUME SHOULD NOT EXCEED EXISTING |
| | CONDITIONS. |
| | |
| | 14. PLEASE PROVIDE AN AUTOTURN ANALYSIS SHOWING THE |
| | DELIVERY TRUCKS WILL BE ABLE TO UTILIZE THE SHOWING |
| | LOADING AREAS. |
| | |
| | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO |
| | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING |
| | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. |
| | |
| | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL |
| | BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC |
| | WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL |
| | APPLICATION FORMS CAN BE DOWNLOADED AT |
| | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ |
| | |
| | 2. SOLID WASTE YARDAGE WILL NEED TO BE VERIFIED AS PART |
| | OF THE FINAL DESIGN TO VERIFY THAT THE DESIGN INCLUDES |
| | APPROPRIATE NUMBER AND SIZE OF TRASH BINS. |
| | |
| | 3. A SEPARATE SUBMITTAL WILL BE REQUIRED TO THE |
| | ENGINEERING DIVISION OF THE PUBLIC WORKS DEPARTMENT FOR |
| | REPLAT APPROVAL. PLEASE CONTACT VINCE NOEL AT |
| | [email protected] TO GET A COPY OF THE PLAT APPLICATION. |
| | FINAL PLAT APPROVAL WILL BE BASED ON THE APPROVED SITE |
| | PLAN. |
| | |
| | |
| | KELLY CRANFORD, P.E. |