Plan Review Notes
Plan Review Notes For Project Z16020010
Project Number Z16020010
Review Stop Z
Sequence Number 1
Notes
Date Text
2016-03-08 12:00:061. PROPOSED PROJECT DOES NOT COMPLY WITH THE MINIMUM
 SIZE OF A DWELLING UNIT OR THE CUMULATIVE AVERAGE SIZE
 OF A DWELLING UNIT AS PRESCRIBED BY SEC 94-109.
 2. PLEASE CORRECT CALCULATIONS FOR ACTIVE USES ALONG
 BANYAN BOULEVARD. PARKING ENTRANCES, MECHANICAL SPACES
 AND STORAGE ARE NOT CONSIDERED ACTIVE USES (SHEET
 A0.01).
 3. PROPOSED PUBLIC OPEN SPACE DOES NOT COMPLY WITH THE
 MINIMUM DIMENSIONS FOR A POS (ONE SIDE NO MORE THAN 5
 TIMES THE OTHER SIDE).
 4. PLEASE INDICATE THE PARKING RAMP PROPOSED SLOPE (SEC
 94-111 (Q)(2) ? NON-PARKING RAMP SLOPE HIGHER THAN 14%
 REQUIRES A BREAK-OVER TRANSITION).
 5. A 20? SIDE SETBACK IS REQUIRED ABOVE THE 5TH STORY.
 6. BLANK WALLS ARE NOT PERMITTED.
 7. PROPOSED CONVENIENCE STORE WILL NOT BE ALLOWED TO
 SALE ALCOHOL (BEER, WINE OR HARD LIQUOR).
 8. PLEASE INDICATE THE TREATMENT OF THE GARAGE ROOFTOP
 THAT WILL NOT BE UTILIZED FOR ROOF GARDEN.
 9. DRIVEWAY SHALL BE MAINTAINED AT THE ADJACENT
 SIDEWALK LEVEL.
 10. PLEASE INDICATE HOW IS THE GARBAGE PICK-UP
 OPERATION (CIRCULATION, STAGING, PRIVATE OR PUBLIC).
 PLEASE PROVIDE AUTO TURN FOR THE LOADING AREAS.
 11. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH PLANAR BREAK REGULATIONS.
 12. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH TRANSPARENCY REGULATIONS.
  
 ADDITIONAL COMMENTS:
 1. PROJECT IS UTILIZING THE TDR PROGRAM, THEREFORE DAC
 SPECIAL REVIEW WILL BE REQUIRED.
 2. SURVEY SHALL INCLUDE MEASUREMENTS OF THE EXISTING
 SIDEWALKS, AND ROW INCLUDING SIDEWALK ACROSS THE STREET
 AND FACE OF BUILDINGS.
 3. THE SITE PLAN DRAWING SHALL INCLUDE THE ADJACENT
 BUILDINGS AND STREET, INCLUDING THE BUILDINGS ACROSS
 THE STREET , AND SHOW THE PROJECT INSERTED IN THE
 CONTEXT.
 4. PLEASE PROVIDE ELECTRONIC DRAWINGS (DXF OR CADD) TO
 ALLOW THE MEASUREMENT OF THE FAR AREA INDICATED IN
 SHEET A0.06.
 5. PLEASE INCLUDE PROPERTY LINES AND SETBACK LINES IN
 ALL FLOOR PLANS AND ELEVATIONS.
 6. PLEASE PROVIDE COLORED ELEVATIONS (ALL FACADES) WITH
 CALL OUT MATERIALS AND REFERENCE PICTURES OF PROPOSED
 MATERIALS (INDICATE SCALE). FACADES SHALL INCLUDE
 ADJACENT BUILDINGS TO SHOW THE PROJECT IN ITS CONTEXT.
 7. RENDERINGS SHALL BE AN ACCURATE REFLECTION OF THE
 SURROUNDING AREA, ACCOUNTING FOR EXISTING STREET
 DIMENSIONS AND SURROUNDING BUILDINGS.
 8. FIRST FLOOR PLAN SHALL INDICATE THE LOCATION OF
 PROPOSED DOORS AND WINDOWS.
  