Plan Review Notes
Plan Review Notes For Project Z16020010
Project Number Z16020010
Review Stop STORM
Sequence Number 1
Notes
Date Text
2017-03-28 12:15:32THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT
 HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?.
 PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS
 WILL NOT IMPACT THE PROPOSED PROJECT.
  
 2. THE FREEBOARD REQUIREMENT FOR STRUCTURES IN A
 SPECIAL FLOOD HAZARD AREA IS ONE FOOT ABOVE BASE FLOOD
 ELEVATION. THE CITY IS CONSIDERING INCREASING THE
 FREEBOARD TO TWO FEET IN THE SPECIAL FLOOD HAZARD
 AREAS.
  
 3. SHOW PIPE INVERTS ON THE FINAL PLANS.
  
 4. PREFERRED CONNECTION OF THE PROPOSED STORM DRAINS IS
 TO THE EXISTING STORM DRAINS IN BANYAN BLVD.
  
 5. PROVIDE A DETAIL OF HOW THE WEIR WILL ATTACH TO THE
 WALLS FOR THE OUTLET PIPE IN THE CORNER OF THE
 STRUCTURE.
  
 6. INDICATE HOW ROOF RUNOFF AND GROUND SURFACE RUNOFF
 WILL BE ROUTED TO THE DRAINAGE SYSTEM.
  
 7. SHOW THE PROPOSED BANYAN BLVD RIGHT-OF-WAY LINE
 (BACK OF EXISTING SIDEWALK?) ON THE SITE PLAN AND
 ENGINEERING PLANS.
  
 8. LANDSCAPE PLANS SHOW BOLLARDS AT EACH END OF THE
 CROSS-BLOCK PASSAGE. HOW WILL THESE AFFECT THE TRUCK
 TRAFFIC EXPECTED IIN THE ALLEY?
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  