| 2016-03-09 12:34:26 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. SHEET A1.01 DOES NOT SHOW HOW PEOPLE EVACUATING THE |
| | BUILDING VIA THE EAST STAIR WILL GET FROM THE STAIR TO |
| | THE STREET WITHOUT TRAVERSING THE PARKING GARAGE. EXIT |
| | DISCHARGE SHALL COMPLY WITH SECTION 1027 OF FLORIDA |
| | BUILDING CODE, |
| | |
| | 3. THE MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES |
| | PROVIDED SHALL BE IN ACCORDANCE WITH FAIR HOUSING ACT |
| | AND SECTION 208.2 OF FLORIDA ACCESSIBILITY CODE. SHEET |
| | A0.01 STATES THAT 8 ACCESSIBLE SPACES WILL BE PROVIDED, |
| | BUT ONLY LEVELS 2 AND 3 ARE SHOWN TO HAVE TWO |
| | ACCESSIBLE SPACES EACH ON SHEET A1.02. |
| | |
| | 4. THERE IS NO ACCESSBLE ROUTE SHOWN FROM THE |
| | ACCESSIBLE PARKING SPACES TO THE BUILDING |
| | ENTRANCE/ELEVATORS. PER SECTION 208.3 OF FLORIDA |
| | ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES ARE TO BE |
| | LOCATED ON THE SHORTEST POSSIBLE ROUTE OF TRAVEL FROM |
| | ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE FOR EACH |
| | BUILDING. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL |
| | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE |
| | |
| | 5. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, |
| | ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A |
| | PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND |
| | DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA |
| | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 |
| | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 6. WHEN ACCESSIBLE ROUTES ARE SHOWN, PLEASE NOTE THAT |
| | ACCESSIBLE PARKING SPACE ACCESS AISLES SHALL BE LOCATED |
| | SO THAT THE USER IS NOT COMPELLED TO WALK OR WHEEL |
| | BEHIND ANOTHER PARKED VEHICLE OR IN THE TRAVEL LANE. |
| | THE ACCESS AISLES SHALL ALSO COMPLY WITH THE OTHER |
| | PROVISIONS OF SECTION OF 502.3 OF FLORIDA ACCESSIBILITY |
| | CODE. |
| | |
| | 7. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE |
| | |
| | 8. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. |
| | |
| | 9. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 10. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 11. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE |
| | ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, |
| | GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: |
| | [email protected] |
| | |
| | 11. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC |
| | PLACES (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION |
| | OF PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, |
| | CONTACT SYBILLE WELTER, ART IN PUBLIC PLACES |
| | COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |