Plan Review Notes
Plan Review Notes For Project Z16020009
Project Number Z16020009
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2016-10-31 14:18:36IN ADDITION TO PREVIOUS ACKNOWLEDGED COMMENTS:
  
 1. THE AUTOTURN ANALYSIS WAS NOT SHOWN FOR WHERE THE
 TRASH COLLECTORS ARE BEING LOCATED. ROOM DOES NOT
 APPEAR LARGE ENOUGH. PLEASE CONTACT FERDINAND RIVERA
 FOR SANITATION APPROVAL.
  
 2. AS PREVIOUSLY DISCUSSED, A NEW WATER MAIN AND SEWER
 LINE WILL NEED TO BE RUN FROM THE EAST PROPERTY LIMITS
 TO CONNECT WITH THE NEW FRONTAGE ROAD ALONG THE FEC.
 THIS IS A REQUIREMENT FOR THE PROPOSED OVERHEAD AND
 SUBSURFACE ALLEY IMPROVEMENTS.
  
 3. THE CITY WILL WORK WITH THE APPLICANT ON THE TYPE OF
 SURFACE REQUIREMENTS FOR THE ALLEY WHEN RESTORED.
  
 4. A PREVIOUS GAS LINE IS NO LONGER SHOWN ON THE
 PLANS.. IS THERE A GAS LINE IN THE ALLEY?
  
 ALL PREVIOUS COMMENTS CONCERNING ADDITIONAL SUBMITTALS
 AND AGREEMENTS STILL PERTAIN.