Plan Review Notes
Plan Review Notes For Project Z16020008
Project Number Z16020008
Review Stop PW
Sequence Number 3
Notes
Date Text
2016-04-28 16:48:21THE SITE PLAN IS APPROVED SUBJECT TO THE FOLLOWING
 CONDITIONS:
  
 1.THE ONSITE WATER MAIN WILL BE A PRIVATE MAIN AND
 WATER USAGE WILL BE MEASURED WITH A MASTER METER FOR
 THE DEVELOPMENT.
  
 2. THE WATER MAIN IS NOT TO BE LOCATED WITHIN THE
 STORMWATER RETENTION AREA.
  
 3. THE GRADING PLAN FOR THE PARKING LOTS ON THE NORTH
 SIDE OF THE SITE ARE TO BE DESIGNED TO DRAIN TOWARD THE
 DRAINAGE SYSTEM OF CATCH BASINS.
  
 4. GRADING OF PHASE 2 ROADWAY ALONG SOUTH PROPERTY LINE
 NOT INCLUDED IN THE SITE PLAN.
  
 5. GRADING PLAN FOR ENGINEERING PERMIT WILL NEED
 ADDITIONAL PROPOSED GRADES FOR THE CORNERS OF THE
 PARKING LOTS.
  
 6. REQUIREMENTS LISTED UNDER THE ORIGINAL APPROVAL
 STILL APPLY.
  
 TRACY L. WARD, P.E.
 PUBLIC WORKS DEPARTMENT
 [email protected]
 (561) 494-1120