Plan Review Notes For Project Z16020008
Project Number Z16020008
Review Stop PW
Sequence Number 2
Notes
Date Text
2016-04-25 12:19:30THE FOLLOWING COMMENTS ARE BASED ON THE REVIEW OF THE
 APRIL 8, 2016 PLAN SUBMITTAL TO PPRC:
 1. SHEET C-1 SHOWS WHAT APPEARS TO BE AN EASEMENT OVER
 THE WATER MAIN. THIS IS INCONSISTENT WITH THE
 ACKNOWLEDGEMENT OF THE ENGINEER THAT THE WATER SYSTEM
 WILL BE MASTER METERED.
  
 2. REVISE THE PROPOSED RETENTION AREA OR WATER MAIN
 ROUTE SO THAT THE WATER MAIN DOES NOT CROSS THE STORM
 RETENTION AREA. PERHAPS THE STORM RETENTION AREA CAN
 INCLUDE INLET D-13 INSTEAD OF D-14, THEREBY ELIMINATING
 THE 90 LF OF 36" RCP THAT WOULD BE REMOVED IN PHASE 2.
  
 3. ENGINEER HAS ACKNOWLEDGED THE NORTH PARKING LOTS
 NEED TO BE RE-GRADED TO DRAIN TO THE STORM INLETS
 INSTEAD OF THE BACK OF THE PARKING SPACES.
  
 4. GRADING OF PHASE 2 ROADWAY ALONG SOUTH PROPERTY LINE
 NOT INCLUDED IN THIS SUBMITTAL.
  
 5. GRADING PLAN FOR ENGINEERING PERMIT WILL NEED
 ADDITIONAL PROPOSED GRADES FOR THE CORNERS OF THE
 PARKING LOTS.
  
 6. ENGINEER EMAILED AN AUTOTURN ANALYSIS DEMONSTRATING
 THE DUMPSTER LOCATION CAN BE READILY SERVICED.
  
 7. REQUIREMENTS LISTED UNDER THE ORIGINAL APPROVAL
 STILL APPLY.
  