| 2016-05-05 15:24:34 | ON REVIEW OF THE RE-SUBMITTAL, THE PREVIUOS COMMENTS BY |
| | FIRE REMAIN APPLICABLE. |
| | |
| | 2ND REVIEW: |
| | |
| | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2 |
| | TEMPORARY OFFICES AND SHEDS SHALL BE SEPARATED FROM |
| | ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH |
| | TABLE 4.2.1. PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM |
| | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE |
| | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE |
| | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH |
| | THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, |
| | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. |
| | |
| | 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, |
| | PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE, |
| | INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE |
| | OCCUPANCIES (PARKING STRUCTURES) |
| | |
| | 7. THE SEPARATION AND OPENING PROTECTION BETWEEN THE |
| | PARKING GARAGE AND RESIDENTIAL AREAS SHALL BE IN |
| | ACCORDANCE AND COMPLIANCE WITH THE SPECIFIC AND MOST |
| | STRINGENT PROVISION REQUIREMENT OF EITHER CHAPTER OF |
| | THE FIRE CODE. |
| | |
| | THESE BUILDINGS IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 |
| | OF NFPA 101 FLORIDA EDITION 2009. FOR NON-SEPARATED |
| | MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE |
| | SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO |
| | THE BUILDING. |
| | |
| | 8. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA |
| | 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS |
| | STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE |
| | BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE |
| | BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED |
| | TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE |
| | PREVENTION BUREAU PRIOR TO ANY INSTALLATION. |
| | |
| | IT IS STRONGLY RECOMMENDED FOR EACH BUILDING HAVE IT'S |
| | OWN FIRE ALARM PANEL AND SYSTEM. |
| | |
| | FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE |
| | PRIMARY AND SECONDARY POWER SOURCES? |
| | |
| | 9. A CLASS A NFPA 72 COMPLIANT MONITORED FIRE ALARM |
| | SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP |
| | DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND |
| | APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY |
| | INSTALLATION. |
| | |
| | 10. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY |
| | ILLUSTRATED ON THE PLAN. |
| | |
| | 11. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING |
| | EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN. |
| | |
| | IF AN EMERGENCY POWER GENERATOR IS PROPOSED, WHAT IS |
| | (ARE) THE PRIMARY AND SECONDARY POWER SOURCES? |
| | |
| | 12. TACTILE SIGNAGE SHALL BE INSTALLED AT ALL EXIT |
| | DOORS. |
| | |
| | 13. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL |
| | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, |
| | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A |
| | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE |
| | SAFETY FEATURES AND EQUIPMENT. |
| | |
| | A REVIEW OF THE SUBMITTED LIFE SAFETY PLAN ON SHEET A |
| | 1.0- 3.0 SHOWS THE EXIT SEPARATION OF THE EXIT |
| | STAIRWELLS THAT DOES NOT COMPLY WITH THE LIFE SAFETY |
| | CODE. THE SEPARATION OF THE EXITS, 50' SHALL BE |
| | MEASURED EXIT DOOR TO EXIT DOOR. |
| | |
| | PER NFPA 101, CHAPTER 7, 7.5.1.3.2, WHERE TWO EXITS, |
| | EXIT ACCESSES, OR EXIT DISCHARGES ARE REQUIRED, THEY |
| | SHALL BE LOCATED AT A DISTANCE FROM ONE ANOTHER NOT |
| | LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL |
| | DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE |
| | SERVED, MEASURED IN A STRAIGHT LINE BETWEEN THE NEAREST |
| | EDGE OF THE EXITS, EXIT ACCESSES, OR EXIT DISCHARGES. |
| | |
| | 14. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF |
| | FIRE PREVENTION. ADDITIONAL HYDRANTS APPEAR TO REQUIRED |
| | AT THE FRONT ACCESS WAY. COORDINATION WITH THE |
| | PREVENTION BUREUA IS STRONGLY ENCOURAGE. |
| | |
| | 15. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS |
| | (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND |
| | COORDINATED WITH THE BUREAU OF FIRE PREVENTION. |
| | ADDITIONAL FDC'S APPEAR TO REQUIRED AT THE FRONT OF |
| | EACH BUILDING. COORDINATION WITH THE PREVENTION BUREUA |
| | IS STRONGLY ENCOURAGE. |
| | |
| | 16. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE |
| | ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED |
| | ON THE PLAN. TWO SEPARATE, SEPARATED WATER SUPPLIES |
| | SHALL BE CLEARLY INDICATED ON THE PLAN. |
| | |
| | ALL SITE FIRE LINES SHALL COMPLY WITH NFPA 24 AND BE |
| | INSPECTED BY THE FIRE PREVENTION BUREAU. |
| | |
| | 17. A FIRE LOAD CALCULATION IS REQUIRED TO ENSURE THAT |
| | THE EXISTING OR PROPOSED WATER SUPPLY IS AVAILABLE FOR |
| | FIRE PROTECTION OF THE PROJECT. |
| | |
| | 18. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS |
| | BUILDING. |
| | |
| | ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, |
| | PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. |
| | |
| | 19. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7 |
| | KEYWAY SYSTEM. |
| | |
| | ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S |
| | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA |
| | B44, SAFETY CODE FOR ELEVATORS. |
| | |
| | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN |
| | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL |
| | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET |
| | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER |
| | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN |
| | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE |
| | IN THE HORIZONTAL POSITION. |
| | |
| | 20. COMMAND ROOM |
| | |
| | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, |
| | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN |
| | THE FOLLOWING FEATURES: |
| | 1. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM |
| | DIMENSION OF 10 FT. |
| | 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| | 3. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | 4. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION |
| | OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| | BARRIERS AND SMOKE PARTITIONS |
| | 5. A WORK TABLE. |
| | 6. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN |
| | FOR THE BUILDING. |
| | 7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| | CONTROL UNIT. |
| | 8. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF |
| | THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| | 9. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION |
| | SYSTEMS. |
| | 10. CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY |
| | 11. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY |
| | PANELS |
| | 12. EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | 13. FIRE PUMP STATUS INDICATORS |
| | 14. GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES. |
| | 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE |
| | 16. CONTROLS REQUIRED FOR SMOKE CONTROL |
| | 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1. |
| | 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| | SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| | PROVIDED |
| | |
| | 21. RADIO |
| | |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| | RADIO ENHANCEMENT SERVICES. |
| | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| | DETERMINED BY THE AHJ. |
| | MAINTAIN A MINIMUM RADIO SIGNAL STRENGTH OF 102.0 DBM |
| | FOR THE RADIO SYSTEM USED BY WEST PALM BEACH FIRE |
| | RESCUE. IF THE MINIMUM CANNOT BE MAINTAINED, A |
| | BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH |
| | A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP. |
| | |
| | 22. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT |
| | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| | |
| | 23. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | PETER LEDUC |