| 2016-05-11 08:19:12 | CITY OF WEST PALM BEACH |
| | ENGINEERING DEPARTMENT |
| | |
| | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO |
| | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING |
| | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. |
| | |
| | 1. PLEASE SUBMIT ESTIMATES FOR THE SOLID WASTE |
| | COLLECTION YARDAGE. |
| | |
| | 2. AS PREVIOUSLY REQUESTED, PROVIDE AN AUTOTURN |
| | ANALYSIS DEMONSTRATING THE SOLID WASTE COLLECTION |
| | VEHICLE CAN ACCESS THE PROPOSED DUMPSTER / COMPACTOR |
| | LOCATIONS AT THE NORTHEAST CORNER OF THE PROPERTY AND |
| | WITHIN THE PARKING GARAGE. THE TRASH |
| | DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY |
| | SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER |
| | PER SECTION 74-35(A)(5) OF THE CODE OF ORDINANCES. IF A |
| | ROLL-OFF COMPACTOR IS PROPOSED, PLEASE PROVIDE A LETTER |
| | FROM THE PRIVATE PROVIDER VERIFYING THAT THEY CAN |
| | PROVIDE SERVICE WITH THE CONFIGURATION SHOWN ON THE |
| | PLANS. |
| | |
| | 3. DETAILS SHEETS WILL NEED TO UTILIZE STANDARD CITY OF |
| | WEST PALM BEACH DETAILS, WHICH MAY BE DOWNLOADED AT |
| | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ |
| | |
| | 4. PLEASE SHOW THE SIGHT TRIANGLES ON THE GROUND FLOOR |
| | LANDSCAPING PLAN FOR THE INTERSECTIONS AND VEHICULAR |
| | EXITS. (SECTION 94-305E, CODE OF ORDINANCES) |
| | |
| | 5. EXISTING UTILITY SERVICE LINES, IF NOT UTILIZED BY |
| | THE SITE REDEVELOPMENT, ARE TO BE REMOVED BACK TO THE |
| | MAIN. (SECTION 2.23 OF THE CITY RIGHT OF WAY |
| | CONSTRUCTION STANDARDS MANUAL) PLEASE ADD THE |
| | APPROPRIATE NOTES TO THE CONSTRUCTION PLAN. |
| | |
| | 6. AS MENTIONED IN OUR ORIGINAL COMMENTS, PLEASE |
| | RELOCATE THE PROPOSED MASTER METER ADJACENT TO PUBLIC |
| | RIGHT-OF-WAY. ON-SITE SUB-METERS WILL REQUIRE APPROVAL |
| | FROM CITY UTILITIES CUSTOMER SERVICE DIVISION. |
| | |
| | 7. AS MENTIONED IN OUR ORIGINAL COMMENTS, PER SECTION |
| | 2.21.2 OF THE CITY RIGHT OF WAY STANDARDS MANUAL, |
| | PROJECTS WHICH DISTURB 40% OR MORE OF A ROADWAY (LINEAR |
| | FOOTAGE) PER BLOCK WILL BE REQUIRED TO MILL AND |
| | RESURFACE THE ENTIRE BLOCK. PLEASE INCLUDE MILLING AND |
| | RESURFACING OF THE HAMPTON ROAD ON THE CONSTRUCTION |
| | PLANS. |
| | |
| | 8. PLEASE REVISE THE DRIVEWAY APRONS ON THE ALLEY TO |
| | MEET THE CITY?S ENGINEERING DESIGN STANDARDS. AN |
| | EXCEPTION TO THE STANDARD MAY BE REQUESTED. HTTP://WPB. |
| | ORG/ENGINEERING/ENGINEERING-SERVICES/ENGINEERING-STANDA |
| | RDS/ |
| | |
| | 9. PLEASE ELIMINATE THE EASTERN DRIVEWAY ON HAMPTON. |
| | THE PROPOSED ENTRANCE IS DOES NOT MEET THE MINIMUM |
| | DISTANCES LISTED IN SECTION 94-313(2) OF THE CITY?S |
| | CODE OF ORDINANCES. |
| | |
| | 10. PLEASE RE-EVALUATE THE PARKING CIRCULATION PLAN. |
| | THE SOUTHEASTERN RETAIL PARKING APPEARS TO UTILIZE |
| | HAMPTON AVENUE AS PART OF THE INTERNAL CIRCULATION |
| | PLAN. |
| | |
| | 11. PLEASE CHECK THE RESIDENTIAL PARKING TOTALS. IN THE |
| | PARKING GARAGE, THE PLANS SHOW 269 PARKING SPOTS ON |
| | LEVEL 1 AND 288 SPOTS ON LEVEL 2 (557 SPOTS). SOME OF |
| | THESE SPOTS WILL NEED TO BE ELIMINATED TO COMPLY WITH |
| | CODE OF ORDINANCES SECTION 94-111, WHICH REQUIRED A |
| | MINIMUM 3 FT BACK UP AREA AT THE TERMINUS OF ANY |
| | DEAD-END DRIVE AISLE PLUS THE EQUIVALENT OF ONE PARKING |
| | SPACE AS A DEDICATE PULL-IN AREA FOR TURNING AROUND. |
| | THE PARKING CALCULATIONS SHOW THAT 625 SPACES WILL BE |
| | PROVIDED IN THE GARAGE. |
| | |
| | 12. THE PLAN ALSO SHOWS 24 SURFACE PARKING SPOTS ON |
| | SOUTH DIXIE. HAVE THESE SPOTS BEEN APPROVED BY FDOT? |
| | |
| | 13. PLEASE ADD STREET NAMES TO ALL PLANS. |
| | |
| | 14. PLEASE PROVIDE UTILITY CROSSING INFORMATION. |
| | |
| | 15. PLEASE PROVIDE FIRE HYDRANT FLOW TEST DATA FROM |
| | EXISTING FIRE HYDRANT ON S DIXIE HWY. |
| | |
| | 16. PLEASE LABEL UTILITY PIPE SIZE AND MATERIAL. |
| | |
| | 17. PLEASE MOVE THE PROPOSED DDCV, REDUCER ASSEMBLY, |
| | AND METER VAULT CLOSER TO THE POINT OF |
| | CONNECTION/ROADWAY R/W. |
| | |
| | 18. PLEASE PROVIDE ENGINEERING/MEP CALCULATION FOR THE |
| | PROPOSED 8? WM SIZING ON HAMPTON ROAD. |
| | |
| | 19. PLEASE PROVIDE PROFILE OF THE PROPOSED 8" WM FROM |
| | THE TAP/POINT OF CONNECTION ON S DIXIE @ HAMPTON ROAD |
| | TO THE METER VAULT. PLEASE CALL OUT THE POINT OF |
| | SERVICE (WATER). |
| | |
| | 20. PLEASE SHOW THE EXISTING 6" WM ON HAMPTON ROAD. IT |
| | IS THE CITY'S PREFERENCE NOT TO HAVE PARALLEL WATER |
| | MAINS AND WILL BE REVIEWING THE NEED FOR MAINTAINING |
| | (2) ACTIVE MAINS ON HAMPTON ROAD. |
| | |
| | 21. PLEASE LABEL THE SIZE AND MATERIAL OF EXISTING |
| | WATER MAIN AND WATER SERVICE CONNECTIONS ON S DIXIE |
| | HWY. RECORD INFORMATION INDICATES THAT THE EXISTING |
| | WATER MAIN ON S DIXIE IS 8" CIP. |
| | |
| | 22. PLEASE PROVIDE ENGINEERING/MEP CALCULATION FOR THE |
| | PROPOSED 8? GRAVITY MAIN SIZING ON HAMPTON ROAD. |
| | |
| | 23. PLEASE CALL OUT THE POINT OF SERVICE (SEWER). CCTV |
| | RECORD (VIDEO AND TV LOG) OF THE PROPOSED SAN SEWER |
| | MAIN WITHIN THE ROADWAY R/W WILL BE REQUIRED AS PART OF |
| | THE PROJECT CLOSE-OUT SUBMITTAL. |
| | |
| | GENERAL COMMENTS |
| | |
| | 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE |
| | AVAILABLE AT HTTP://WWW.CO.PALM-BEACH.FL.US/NEWSROOM/08 |
| | 14/08-26-14-FLOOD_MAPS.HTM. PLEASE REVIEW THE MAPS AND |
| | VERIFY THAT THE NEW MAPS WILL NOT IMPACT THE PROPOSED |
| | PROJECT. |
| | |
| | 2. FDOT APPROVAL WILL BE REQUIRED FOR THE DRAINAGE AND |
| | DRIVEWAY CONNECTIONS OFF OF DIXIE. |
| | |
| | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO |
| | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING |
| | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. |
| | |
| | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL |
| | BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC |
| | WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL |
| | APPLICATION FORMS CAN BE DOWNLOADED AT |
| | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ |
| | |
| | 2. SOLID WASTE YARDAGE WILL NEED TO BE VERIFIED AS PART |
| | OF THE FINAL DESIGN TO VERIFY THAT THE DESIGN INCLUDES |
| | APPROPRIATE NUMBER AND SIZE OF TRASH BINS. |
| | |
| | KELLY CRANFORD, P.E. |
| | CAPITAL IMPROVEMENT PLAN MANAGER |
| | [email protected] |
| | 561-494-1098 (OFFICE) |
| | |
| | VINCE NOEL, PSM |