| Date |
Text |
| 2016-05-10 21:37:49 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. YOUR COMMENT RESPONSE HAS ACKNOWLEDGED THE FOLLOWING |
| | ORIGIANL COMMENT: THIS REVIEW IS A CURSORY REVIEW AS IT |
| | RELATES TO THE SITE. IT IS NOT A REVIEW FOR FULL |
| | COMPLIANCE WITH FLORIDA BUILDING CODE. THE FOLLOWING |
| | COMMENTS ARE TO BE ADDRESSED FOR PERMITTING. |
| | |
| | 2. YOUR COMMENT RESPONSE REGARDING THE ACCESSIBLE |
| | PARKING AND ACCESS TO THE AMENITIES BUILDING IS NOTED, |
| | BUT FAILS TO ADDRESS THE COMMENT FULLY. THE PARKING |
| | COMPUTATION TABLE ON SHEET FSP-1 STATES THAT 13 |
| | ACCESSIBLE SPACES WILL BE PROVIDED ON THE 1ST LEVEL AND |
| | 7 ACCESSIBLE PARKING SPACES WILL BE PROVIDED ON THE 2ND |
| | LEVEL, BUT THE LOCATION OF THOSE SPACES ARE NOT SHOWN |
| | ON SHEETS FSP-1, FSP-2, SP-1, LVL-2, LVL-3, THAT IS |
| | SHOWN ON SHEET LVL-3 APPEAR TO BE LOCATED IN THE |
| | PARKING GARAGE AT LVL-2. THOSE SHEETS ONLY SHOW 9 |
| | ACCESSIBLE SPACES ON THE 1ST LEVEL AND NO ACCESSIBLE |
| | PARKING SPACES ON THE 2ND LEVEL. THE MINIMUM NUMBER OF |
| | ACCESSIBLE PARKING SPACES PROVIDED SHALL BE IN |
| | ACCORDANCE WITH SECTION 208.2 OF FLORIDA ACCESSIBILITY |
| | CODE. |
| | |
| | 3. YOUR COMMENT RESPONSE HAS ACKNOWLEDGED THE FOLLOWING |
| | ORIGIANL COMMENT: PER SECTION 208.2.4 OF FLORIDA |
| | ACCESSIBILITY CODE, ONE IN EVERY SIX ACCESSIBLE SPACES |
| | (AT LEAST ONE) IN A PARKING STRUCTURE, SHALL BE VAN |
| | ACCESSIBLE AND DESIGNED IN ACCORDANCE WITH SECTION OF |
| | 502 OF FLORIDA ACCESSIBILITY CODE (VERTICAL CLEARANCE |
| | NOT LESS THAN 98 INCHES AT SPACE AND VEHICULAR ACCESS |
| | ROUTE) |
| | |
| | 4. YOUR COMMENT RESPONSE HAS ACKNOWLEDGED THE FOLLOWING |
| | ORIGIANL COMMENT: WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE |
| | |
| | 5. YOUR COMMENT RESPONSE HAS ACKNOWLEDGED THE FOLLOWING |
| | ORIGIANL COMMENT: WHEN SUBMITTED FOR BUILDING PERMIT, |
| | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF |
| | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF |
| | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE |
| | VERIFIED. |
| | |
| | 6. YOUR COMMENT RESPONSE HAS ACKNOWLEDGED THE FOLLOWING |
| | ORIGIANL COMMENT: THE PARKING GARAGE APPEARS TO BE AN |
| | OPEN "VENTED" GARAGE. THE REMAINDER OF THIS COMMENT |
| | ONLY APPLIES IF IT IS IN FACT AN ENCLOSED PARKING |
| | GARAGE. IF THE PARKING GARAGE DOES NOT HAVE WALL |
| | OPENINGS, OR SUFFICIENT WALL OPENINGS TO MEET THE |
| | DEFINITION OF AN OPEN PARKING GARAGE, IT WILL BE |
| | CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 5. YOUR COMMENT RESPONSE HAS ACKNOWLEDGED THE FOLLOWING |
| | ORIGIANL COMMENT: SEPARATE PERMITS REQUIRED. ALL |
| | APPLICABLE PERMITS AND SUB-PERMITS MUST BE OBTAINED |
| | BEFORE COMMENCING THE WORK. SEPARATE PERMITS, PLANS AND |
| | FEES, ARE REQUIRED FOR SIGNS, SWIMMING POOLS AND SPAS, |
| | GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, FIRE |
| | SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, GREASE |
| | INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, SITE |
| | IRRIGATION, ETC. |
| | |
| | 6. YOUR COMMENT RESPONSE HAS ACKNOWLEDGED THE FOLLOWING |
| | ORIGIANL COMMENT: EACH SEPARATE BUILDING SHALL HAVE A |
| | SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT |
| | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 |
| | 1080, OR BY EMAIL: [email protected] |
| | |
| | 7. YOUR COMMENT RESPONSE HAS ACKNOWLEDGED THE FOLLOWING |
| | ORIGIANL COMMENT: THIS PROJECT WILL BE SUBJECT TO ART |
| | IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE ON THE |
| | PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP |
| | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC |
| | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |
Print |