Plan Review Notes
Plan Review Notes For Project Z15120017
Project Number Z15120017
Review Stop PU
Sequence Number 1
Notes
Date Text
2016-06-10 17:12:26THIS IS A PRELIMINARY REVIEW OF THE CONCEPTUAL PLANS
 RESUBMITTAL DATED MAY 2016. THE FOLLOWING COMMENTS ARE
 TO BE ADDRESSED PRIOR TO ENGINEERING DEVELOPMENT
 APPROVAL:
  
 1. RECORD INFORMATION INDICATES THAT THE EXISTING WATER
 MAIN ON HAMPTON ROAD IS A DEAD END MAIN. THE EXISTING
 6-INCH WATER MAIN REDUCES TO A 3-INCH WATER MAIN
 APPROXIMATELY 340 FEET FROM S. DIXIE HIGHWAY AND
 TERMINATES AT THE LAST WATER SERVICE JUST EAST OF THE
 RAILROAD RIGHT-OF-WAY. BOTH WERE INSTALLED IN 1940'S.
 THE INITIAL CONCEPTUAL PLAN SUBMITTAL DATED APRIL 2016
 SHOWED APPROX. 180 LF OF NEW 8-INCH WATER MAIN FROM S.
 DIXIE HIGHWAY TO SERVE THE PROPOSED DEVELOPMENT. PLEASE
 EXTEND THE NEW 8-INCH WATER MAIN APPROX. 240 LF BEYOND
 THE PROPOSED 8-INCH FIRE LINE SERVICE CONNECTION.
 ABANDON THE EXISTING WATER MAINS AND TRANSFER ALL
 EXISTING SERVICE CONNECTIONS TO THE NEW WATER MAIN.
 2. PLEASE ADD A BACKFLOW DEVICE FOR EACH OF THE
 PROPOSED WATER SERVICE THAT WILL SERVE A WATER FEATURE;
 3. PLEASE NOTE THAT THE CITY IS EVALUATING IMPACTS TO
 THE WATER AND SEWER SYSTEMS DUE TO INCREASED DEMANDS.
  
 LAURA LE, P.E.
 PUBLIC UTILITIES ENGINEER
  