| 2015-12-17 22:03:24 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. THE EXIT ROUTE FROM THE NORTH STAIR TO THE |
| | RIGHT-OF-WAY SHALL HAVE SEPARATION FROM THE SOUTH STAIR |
| | EXIT ROUTE, SHEET A2.01 DOES NOT SHOW THE PROPOSED EXIT |
| | ROUTE, AND IT APPEARS THAT THE EXIT ROUTE FROM THE |
| | NORTH STAIR WOULD TAKE THOSE EVACUATING THE BUILDING |
| | THROUGH THE LOBBY AND PAST THE SOUTH STAIR ONTO THE |
| | SIDEWALK ON 2ND STREET. PER SECTION 1021.3 OF FLORIDA |
| | BUILDING CODE, EXITS SHALL BE SEPARATED BY A DISTANCE |
| | NO LESS THAN ONE-THIRD OF THE BUILDING DIAGONAL |
| | DIMENSION IN SPRINKLER PROTECTED BUILDINGS. |
| | |
| | 3. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT |
| | LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS |
| | 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE |
| | PUBLIC RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR |
| | FACILITY ENTRANCES. THE VEHICULAR DRIVEWAY SHALL NOT BE |
| | THE ONLY PEDESTRIAN AND WHEELCHAIR ACCESS TO THE |
| | BUILDING. |
| | |
| | 4. WHEN THE WHEELCHAIR ACCESS ROUTE IS SHOWN ON THE |
| | PLANS, ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE |
| | GREATER THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL |
| | COMPLY WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 5. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, |
| | ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A |
| | PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND |
| | DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA |
| | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 |
| | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE). THE ONE |
| | PROVIDED ACCESSIBLE PARKING SPACE SHALL BE VAN |
| | ACCESSIBLE. |
| | |
| | 6. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE |
| | |
| | 7. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. |
| | |
| | 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 9. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES |
| | (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF |
| | PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT |
| | SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT |
| | (561) 822-1521, OR BY EMAIL: [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |