Review Stop STORM
Sequence Number 1
Notes
Date Text
2015-12-09 16:07:241. THE SWALE STORAGE VOLUMES FOR SWALES 'A' AND 'B'
 SHOWN IN THE DRAINAGE CALCULATIONS BOX ON SHEET SP-2
 MAY BE OFF BY A FACTOR OF 12. FOR EXAMPLE, SWALE 'B' IS
 SHOWN TO HAVE A (TOP?) SURFACE AREA OF 584 S.F. ON THE
 SITE PLAN. THE TYPICAL SWALE SECTION INDICATES THE
 SWALE DEPTH WILL BE 6 INCHES OR 0.5 FEET. THE VOLUME
 WOULD BE CLOSER TO 270 C.F. INSTEAD OF 3,234 C.F. SHOWN
 IN THE DRAINAGE CALCULATIONS BOX.
  
 2. CORRECTING THE SWALE VOLUMES IN #1 ABOVE RESULTS IN
 THE SWALES PROVIDING ONLY 40% OF THE REQUIRED STORM
 WATER TREATMENT VOLUME (UTILIZING 50% FOR DRY
 RETENTION). INDICATE HOW THE REQUIRED STORM WATER
 TREATMENT VOLUME WILL BE STORED ONSITE.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 PUBLIC WORKS DEPARTMENT