2015-10-29 16:42:03PERMIT # Z15100028
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) IT IS UNCLEAR, BASED ON THE PLANS SUBMITTED, WHAT
 HAS ALREADY BEEN APPROVED THROUGH PPRC AND WHAT IS
 BEING PROPOSED AS PART OF THIS NEW REQUEST.
  
 2) THERE IS A CONCERN REGARDING ACCESSIBILITY FOR FIRE
 DEPARTMENT VEHICLES TO CIRCULATE THE ENTIRE PERIMETER
 OF THE PROPERTY AND BUILDINGS.
  
 3) 20 FOOT CLEARANCE IN WIDTH IS REQUIRED AT ALL GATES
 FOR FIRE DEPARTMENT ACCESS.
 PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT
 ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO
 ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 32 TONS.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT
 LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
  
 4) KNOX BOX/KNOX KEY SWITCH WILL BE REQUIRED AT ALL
 ACCESSIBLE GATES.
  