Plan Review Notes
Plan Review Notes For Project Z15100025
Project Number Z15100025
Review Stop Z
Sequence Number 3
Notes
Date Text
2016-05-16 12:03:38COMMENTS 3RD REVIEW 5-16-2016
 1. SHEET A1.1A SHALL BE MODIFIED TO ACCURATELY INDICATE
 THE AREAS COUNTED AS FAR ACCORDING TO THE GROSS
 BUILDING AREA DEFINITION IN SEC 94-109 OF THE ZLDRS.
 HATCHED AREAS IN EACH FLOOR PLAN SHALL ONLY INCLUDE
 THOSE AREAS INCLUDED IN GBA. SUMMARY TABLE SHALL HAVE
 ALSO A SEPARATE COLUMN FOR MECHANICAL AND PARKING AREAS
 NOT INCLUDED IN GBA.
 2. PARKING REQUIREMENT TABLE IN SHEET A1.1A SHALL BE
 ADJUSTED TO REFLECT THE CODE REQUIREMENT FOR DOWNTOWN
 (TABLE IV-9).
 3. PLEASE REVISE THE PARKING LAYOUT TO CONFIRM
 COMPLIANCE WITH MINIMUM WIDTH OF PARKING SPACES IN
 THOSE CASES WHERE PARKING SPACE IS ADJACENT TO A COLUMN
 OR A WALL (94-111(C)(1). STRIPING SHALL COMPLY WITH
 CITY DETAIL.
 4. EAST ELEVATION SHOWS WINDOWN IN THE SE ROOM BUT THEY
 ARE NOT SHOWN IN THE FLOOR PLANS. PLEASE CLARIFY AND
 CONFIRM COMPLIANCE WITH BLANK WALL REGULATIONS.
 5. PLEASE INDICATE THE DEPTH OF THE ARCHITECTURAL
 FEATURES PROVIDED ON THE WALLS LESS THAN 3 FEET FROM
 THE PROPERTY LINE.
 6. FENESTRATION SHALL BE PROVIDED ON ALL FACADES
 ENCLOSING ACTIVE USES (2ND FLOOR MANAGER ROOM).
 7. PLEASE IDENTIFY THE PRELIMINARY LOCATION FOR
 COMPLIANCE WITH THE ART IN PUBLIC PLACES REQUIREMENT
 (CONTACT SYBLLE WELTER, ART IN PUBLIC PLACES
 COORDINATOR AT 822-1515).
 8. PLEASE TALK WITH TRACY WARD IN THE ENGINEERING
 DEPARTMENT TO MODIFY THE DESIGN OF THE EXFILTRATION
 TRENCH TO BE BELOW THE STRUCTURAL SOIL DEPTH (36")
 REQUIRED FOR STREET TREES ON TRINITY PLACE.
 9. PLEASE REDUCE THE SEPARATION OF THE TWO TREES IN
 FRONT OF THE HOTEL ENTRANCE TO A MORE CONSISTENT
 SPACING MATCHING THE OTHER TREES AS CLOSE AS POSSIBLE.
 WE RECOMMEND AROUND 35-40 FEET.
 11. PLEASE PROVIDE A HARDSCAPE DRAWINGS FOR DIXIE AND
 TRINITY. TRINITY PLACE SHALL MATCH THE EXISTING PATTERN
 ON THE EAST SIDE OF THE PROPERTY.
 12. SUBMITTED RENDERING ARE STILL NOT ACCURATELY
 REFLECTING THE EXISTING CONTEXT AND THE PROPOSED GROUND
 LEVEL CONDITIONS RESULTING FROM THE BUILDING.
 13. PLEASE PROVIDE PICTURES OF THE PROPOSED BUILDING
 MATERIALS INCLUDING THE GARAGE SCREENING.
  
 13. ARCHITECTURAL DESIGN COMMENTS:
 A. THE REVISED DESIGN HAS INTRODUCED ADDITIONAL
 ARCHITECTURAL LANGUAGE TO THE BUILDING DESIGN RESULTING
 IN DIFFERENT TREATMENT FOR EACH ELEVATION, AND IN
 DETRIMENT OF A MORE CONSISTENT OVERALL BUILDING DESIGN.
 REVISIONS TO THE FACADE DESIGN SHALL BE INTRODUCED.
 B. THE REQUIRED PLANAR BREAK ALONG TRINITY PLACE SHALL
 BE USED ON THE HIERARCHICAL TREATMENT OF THE BUILDING
 ELEMENTS. THE PROPOSED PLANAR BREAK IS LOCATED WHERE
 THE BUILDING ENTRANCE IS, AND AS SUCH IT SHOULD REFLECT
 OR CREATE A SIGNIFICANT ACCENT ON THE FACADE.
 C. ENTRANCE CANOPY SHALL BE LOWERED TO CREATE A
 PEDESTRIAN ENVIRONMENT AND SCALE.
 D. THE DIXIE HWAY FIRST FLOOR ELEVATION SHALL BE
 ADJUSTED TO REFLECT THE PROPOSED RESTAURANT AND
 HIGHLIGHT ITS ENTRANCE.
  
  
 COMMENTS 2ND REVIEW 1-20-2016:
 1. SATISFIED - PLEASE EXTEND THE SPECIALTY TREATMENT OF
 THE SIDEWALK ACROSS THE SOUTH CURB CUT. SHEET A2.1
 SHALL BE ADJUSTED TO REFLECT THE FLUSH CONDITION OF THE
 DRIVEWAY AS IT MEETS SIDEWALK.
  
 COMMENTS 1ST REVIEW 11-10-2015
 1. SATISFIED- 1. EXISTING BACK OF CURB ON TRINITY PLACE
 ALONG THE CITY PLAZA II BUILDING SHALL BE CONTINUED
 WEST AND ADJUSTED IN FRONT OF THE CANOPY HOTEL IF
 NECESSARY. NEW CURB CUT WILL BE THE NEW BACK OF CURB
 FOR THE PURPOSES OF MEASURING THE SETBACK REQUIREMENTS.
 2. SATISFIED- 2. TRAVEL LANE WIDTH SHALL BE MAINTAINED
 CONSISTENT FROM OLIVE AVE TO DIXIE HWAY AND CURB SHALL
 BE ADJUSTED IF NECESSARY.
 3. SATISFIED- 3. SETBACKS ARE MEASURED FROM BACK OF
 CURB (EXISTING CURB ON DIXIE HWAY, AND NEW CURB ON
 TRINITY PLACE).
 4. SATISFIED- 4. DOORS SHALL NOT SWING OVER THE MINIMUM
 REQUIRED SETBACK.
 5. UNDER REVIEW BY TE-5. PLEASE EXPLAIN HOW THE PARKING
 OPERATION IS GOING TO FUNCTION. SOME CONCERNS ARE:
 - CARS WAITING FOR THE ELEVATOR SHALL NOT BE STACKED
 IN THE PUBLIC ROW.
 - HOW LONG DOES IT TAKE FOR THE ELEVATOR TO GO UP AND
 DOWN?
 - WHAT HAPPENS IF THE ELEVATOR BREAKS DOWN?
 6. SATISFIED- DAC VARIANCE NOT NEEDED- 6. ACTIVE USES
 ARE REQUIRED ALONG 60% OF DIXIE HWAY ON ALL FLOORS UP
 TO 5TH STORY. PROJECT IS PROPOSEING PARKING USES ON
 FLOORS 3RD TO 5TH.
 7. SATISFIED- DAC VARIANCE NOT NEEDED- 7. PARKING IS
 ALLOWED ABOVE THE 5TH STORY WITHOUT ACTIVE USES, BUT A
 CONDITIONAL SETBACK OF 31' IS REQUIRED.
 8. SATISFIED- DAC VARIANCE NOT NEEDED- 8. PARKING IS
 ALLOWED ABOVE THE 5TH STORY WITHOUT ACTIVE USES, BUT A
 CONDITIONAL SETBACK OF 27? IS REQUIRED.
 9. NOT SATISFIED- EAST ELEVATION IS A BLANK WALL NOT
 PERMITTED BY THE CURRENT CODE.FURTHER DISCUSSION IS
 NECESSARY ON THIS ITEM.HOW IS THE INDICATED PLANNAR
 BREAK ON GARAGE FACING TRINITY PLACE REFLECTED ON THE
 FACADE? - 9. PLEASE PROVIDE INFORMATION TO CONFIRM
 COMPLIANCE WITH THE FACADE ARTICULATION REQUIREMENTS.
 PLEASE CONFIRM COMPLIANCE WITH FENESTRATION
 REQUIREMENTS AND COMPLIANCE WITH PROHIBITION FOR BLANK
 WALLS.
 10. SATISFIED-FURTHER DISCUSSION ON OPERATION
 NECESSARY. - 10. PROPOSED HOTEL IS NOT PROVIDING ANY
 LOADING AREA. PLEASE EXPLAIN HOW THE HOTEL IS GOING TO
 BE SERVICED WITHOUT A DEDICATED LOADING AREA. TRINITY
 PLACE IS A SINGLE LANE ROAD AND IT CANNOT BE BLOCK AT
 ANY TIME.
 11. SATISFIED-FURTHER DISCUSSION NECESSARY- 11. HOW IS
 THE PROJECT PROPOSING TO HANDLE GARBAGE COLLECTION?
 12. EAST ELEVATION SHOWN SOME ADDITIONAL WINDOWS ON THE
 SE ROOMS. PLEASE CLARIFY WHAT TYPE OF OPENING ARE
 PROPOSED AND INDICATE THEM IN THE FLOOR PLANS. PODIUM
 HEIGHT IS ACCEPTABLE, FURTHER DISCUSSION NECESSARY
 REGARDING THE BLANK WALL FACING CITY PLAZA II.12. -
 COMPATIBILITY WITH ADJACENT CITYPLAZA II BUILDING.
 FURTHER DISCUSSION NEEDED REGARDING THE PODIUM HEIGHT
 IN RELATION WITH THE CPII PODIUM HEIGHT, AND THE
 RELATIONSHIP OF SOME DESIGN ELEMENTS BETWEEN THE TWO
 BUILDINGS. THE GOAL IS TO MAKE THE ENTIRE BLOCK TO WORK
 AS A CONSISTENT URBAN BLOCK.
 13. SATISFIED. MECHANICAL SCREENING AND SOUND
 ATTENUATION FOR ALL MECHANICAL WILL BE REQUIRED.- 13.
 PLEASE EXPLAIN ANY ACTIONS TAKEN TO MINIMIZE THE NOISE
 AND LIGHT POLLUTION FROM THE ROOFTOP TERRACES INTO THE
 ADJACENT RESIDENTIAL BUILDING.
 14. SATISFIED. A FENCE WILL BE REQUIRED TO CONTROL
 ACCESS TO THE BACK OF CITY PLAZA II AND CANOPY HOTEL.-
 14. PLEASE PROVIDE ANY INFORMATION ON HOW THE REAR AND
 SIDE SETBACKS ARE GOING TO BE TREATED AT GROUND LEVEL.
 THERE SEEM TO BE SOME ODD LEFT OVER AREAS.
 15. SATISFIED, PLEASE PROVIDE A HARDSCAPE DRAWING.
 PLEASE PROVIDE HARDSCAPE DRAWINGS WITH DETAILS. LIGHT
 FIXTURE AND POLE ALONG TRINITY PLACE SHALL MATCH CITY
 PLAZA II, ALONG DIXIE HWAY SHALL MATCH DIXIE HWAY
 FIXTURE AND POLE.- 15. SIDEWALK TREATMENT ON TRINITY
 PLACE SHALL CONTINUE THE EXISTING TREATMENT/PATTERN ON
 THE EAST SIDE.
 16. SATISFIED.- 16. IS THE GROUND FLOOR RESTAURANT
 PROPOSED WITH ACCESS FROM DIXIE HWAY AND OUTDOOR
 SEATING?
 SUBMITTAL COMMENTS:
 1. OK.-1. PLEASE PROVIDE REDUCED DIAGRAMS OF EVERY
 FLOOR INDICATING THE AREAS THAT ARE COUNTED AS PART OF
 THE GROSS BUILDING AREA AND THE AREAS THAT ARE NOT.
 INCLUDE SQUARE FOOTAGE IN A SUMMARY TABLE.
 2. ELEVATIONS SHALL HAVE SHADOWS AND INCLUDE THE
 CONXTEXT IN THE SAME BLOCK AND AT LEAST 200' ACROSS THE
 ADJACENT STREETS. - 2. PLEASE PROVIDE COLORED
 ELEVATIONS WITH THE SURROUNDING CONTEXT. ELEVATIONS
 SHALL CONTAIN INFORMATION TO INDICATE ANY PLANAR BREAKS
 AND ITS DEPTH.
 3. SUBMITTED PEDESTRIAN RENDERINGS DO NOT SEEM ACCURATE
 TO THE SURROUNDING CONTEXT. SHEET A5.3 SHOWS TRINITY
 PLACE AS TWO LANE ROAD WITH A WIDE SIDEWALK ON THE
 NORTH SITE, WHICH IS NOT THE CASE. PLEASE MODIFY ANY
 PERSPECTIVES OR RENDERINGD TO ACCURATELY REFLECT THE
 CONTEXT AS WELL AS THE PROPOSED LANDSCAPE AND HARDSCAPE
 FOR THE PROJECT (SIDEWALK DIMENSIONS). - 3. PLEASE
 PROVIDE PEDESTRIAN LEVEL RENDERINGS OF THE PROPOSED
 HOTEL.
 4. NEED ADDITIONAL PICTURES OF GARAGE SCREENING
 MATERIAL - 4. PLEASE PROVIDE IMAGES OF PROPOSED FACADE
 MATERIALS AND GARAGE ARCHITECTURAL TREATMENT WITH
 GENERAL INFORMATION ON PROPOSED MATERIAL.
  
  