Plan Review Notes
Plan Review Notes For Project Z15100013
Project Number Z15100013
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2015-11-24 16:16:01AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED
 11.17.15, FROM ANDERSON ARCHITECTURE, INC, TO THE CITY
 OF WEST PALM BEACH, THE PREVIOUSLY SUBMITTED FIRE
 PREVENTION BUREAU COMMENTS HAVE BEEN ADDRESSED WITH THE
 FOLLOWING ADDITIONALL COMMENTS.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. IS THE SCREENING FOR THE HITTING CAGE FIRE
 RETARDENT?
  
 THE APPLICANT PROVIDED THAT IT IS NOT AND HAS A MELTING
 POINT OF 482 DEGRESS F. THE APPLICANT IS STRONGLY
 ENCOURAGED TO RESEACH AND INSTALL A FIRE RETARDENT
 SCEEN OR APPLY A FIRE RETARDENT MATERIAL ONTO THE
 SCREEN FOR FIRE AND LIFE SAFETY PURPOSES. THE POTENTIAL
 FOR A RAPID BURNING SURFACE AREA IS EXTREMELY HIGH IN
 THE EVENT THE SCEEN WERE TO INTERACT WITH A IGNITION
 SOURCE, I.E. A BICK BUTANE HAND LIGHTER FLAME BURNS AT
 600 DEGREES. THE SCREEN WILL FAIL AND MELT AROUND
 ANYONE WHO IS UNDER IT.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 2. NO SMOKING SIGNS SHALL BE INSTALLED AT THE FRONT OF
 THE HITTING CAGE.
  
 ADDRESSED
  
 3. A FIRE EXTINGUSIHERS SHALL BE INSTALLED AT EACH SIDE
 OF THE FRONT OF THE HITTING CAGE.
  
 ADDRESSED
  