2017-09-20 10:25:26THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS WILL BE REVIEWED AS PART OF THE ENGINEERING
 DEVELOPMENT APPROVAL AND BUILDING PERMIT APPLICATION
 PROCESS. THE FOLLOWING COMMENTS NEED TO BE ADDRESSED
 PRIOR TO SITE PLAN APPROVAL:
 - SHEET A-201 ? REMOVE 90 DEGREE PARKING SPACE DETAIL
 AND REPLACE WITH PARALLEL PARKING DETAIL.
 - THE ADA PARKING SPACE ON BUNKER IS NOT ACCESSIBLE.
 PREFERABLY THE PARKING SPACE SHOULD BE 13? WIDE AND A
 60" WIDE ACCESS AISLE MUST BE PROVIDED. DETAILS OF
 ACCESSIBLE ON STREET PARALLEL PARKING SPACES CAN BE
 FOUND AT:
 HTTPS://WWW.ACCESS-BOARD.GOV/GUIDELINES-AND-STANDARDS/S
 TREETS-SIDEWALKS/PUBLIC-RIGHTS-OF-WAY/BACKGROUND/ACCESS
 -ADVISORY-COMMITTEE-FINAL-REPORT/X02-6-VEHICULAR-WAYS-A
 ND-FACILITIES
  
 -LABEL WIDTH AND LENGTH OF PARALLEL PARKING SPACES.
 - PROVIDE A PAVEMENT MARKING PLAN FOR REVIEW. SHOW ALL
 OF BUNKER ROAD. SHOW LANE WIDTHS, PAVEMENT MARKINGS,
 AND DISTANCE OF PARALLEL PARKING SPACES FROM A FIXED
 POINT, E.G. POINT OF TANGENCY OF CURB RETURN.
 - LABEL SIDEWALK WIDTH
 - SHEET C-01, PROVIDE DRIVEWAY PROFILE. NOTE THAT CITY
 DETAIL CWPB NO-GC-7 ISN?T ADA COMPLIANT FOR NARROW
 SIDEWALKS.
 - WHY ARE TWO DRIVEWAYS PROPOSED ON WEBSTER?
 - WHY IS THERE A LARGE DROP CURB PROPOSED AT THE SOUTH
 ENTRANCE OF WEBSTER? ONLY TWO DOORS ARE SHOWN ON
 BUILDING.
 - WILL LOADING ON WEBSTER BLOCK SIDEWALK?
 - BUNKER ROAD, REVIEW ADA ACCESSIBILITY OF SIDEWALK. IT
 APPEARS THE EXISTING CURB RAMP AT THE EAST END OF THE
 PROPERTY IS NOT ADA COMPLIANT.
  
 ERIK D. FERGUSON, P.E.
 SENIOR PROJECT ENGINEER