Plan Review Notes For Project Z15090024
Project Number Z15090024
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2015-11-16 13:44:45RECOMMEND APPROVAL WITH THE FOLLOWING CONDITIONS:
  
 1. DUMPSTER ENCLOSURE INSIDE CLEARANCE MUST BE A
 MINIMUM OF 12.5 FT.
  
 2. A PRELIMINARY ENGINEERING PLANS (WATER, SEWER,
 PAVING, AND DRAINAGE) WAS NOT SUBMITTED. WATER AND
 SEWER CONNECTION LOCATIONS SHOWN ON THE PLANTING PLAN
 ARE NOT INCLUDED IN THE SITE PLAN APPROVAL.
  
 3. PALM BEACH COUNTY APPROVAL OF THE PROPOSED
 STORMWATER CONNECTION WILL IS REQUIRED PRIOR TO
 ENGINEERING DEVELOPMENT APPLICATION APPROVAL.
  
 4. PRIOR TO START OF CONSTRUCTION, SEPARATE SUBMITTALS
 ARE REQUIRED TO THE ENGINEERING DIVISION OF THE PUBLIC
 WORKS DEPARTMENT FOR ENGINEERING DEVELOPMENT APPROVAL
 AND UNITY OF TITLE APPROVAL. THE APPLICATION FORMS CAN
 BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
  
  
 PROJECT SUMMARY: 1.7 ACRES, 110,838 SF OF SELF-STORAGE
 WATER DEMAND BASED ON 0.01 GALLONS PER SF = 1,108 GPD,
 PEAK FLOW (X 2.5) = 115 GPH
 SANITARY SAME AS POTABLE
 SOLID WASTE = 7 LBS PER DAY PER 100 SF = 7,760 LBS PER
 DAY
 NEW PEAK HR TRIPS: 13 (7/6) AND 26 (14/12)