Plan Review Notes
Plan Review Notes For Project Z15090018
Project Number Z15090018
Review Stop Z
Sequence Number 4
Notes
Date Text
2017-03-28 09:54:18CASE NO. PB 950SSSS
 HILTON CONVENTION CENTER HOTEL LOADING AREA - C.O.
 REVIEW
 600 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) FULL SIZED PAPER COPIES AND AN ELECTRONIC COPY IN
 .PDF FORMAT OF ALL PLANS. PLEASE NOTE THAT CHANGES ON
 THE RESUBMITTED PLANS OR THE SUBMITTAL OF
 INFORMATION/PLANS TO ADDRESS THE COMMENTS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ACCESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($60).
  
 1) THE WALL PORTION OF THIS APPLICATION IS STILL
 OUTSTANDING AND IS PREVENTING THE APPROVAL OF THE MINOR
 AMENDMENT.
  
 2) THE BUILDING PERMIT FOR THE CMU WALL (15080551) IS
 SHOWN AS EXPIRED IN THE CITY'S RECORDS. THIS PERMIT
 NEEDS TO BE ACTIVATED, REVIEWED, APPROVED AND THE
 INSPECTIONS PASSED FOR THE WALL.
  
 3) REPEAT COMMENT: THE PLANS SUBMITTED TO DATE FOR THE
 MINOR AMENDMENT AND THE PERMIT DO NOT MATCH. THERE ARE
 VARIOUS CONFLICTING WALL HEIGHTS SHOWN RANGING FROM SIX
 (6) FEET IN HEIGHT TO 11 FEET IN HEIGHT. ALL PLANS
 SHALL MATCH AND SHOW THE FINAL WALL CONFIGURATION.
  