| 2015-09-08 20:19:06 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. THE SURVEY DRAWING SHOWS PROPERTY LINES IN |
| | TTRAVERSING THE FOOTPRINT OF THE PROPOSED BUILDINGS. |
| | FOR ANY BUILDING CROSSING A PROPERTY LINE, EITHER A |
| | RECORDED UNITY OF TITLE, OR SOME OTHER APPROVED LEGAL |
| | INSTRUMENT, SHALL BE INCLUDED WITH THE PERMIT |
| | APPLICATION, OR THE BUILDING MUST HAVE A FIRE WALL |
| | ALONG THE PROPERTY LINE, PER SECTION 202 OF FLORIDA |
| | BUILDING CODE, BUILDING, FIRE SEPARATION DISTANCE. |
| | |
| | 3. THE BUILDING ENTRANCES ARE NOT YET IDENTIFIED ON THE |
| | PLANS. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW |
| | AT LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS |
| | 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE |
| | PUBLIC RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR |
| | FACILITY ENTRANCES. |
| | |
| | 4. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT |
| | LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS |
| | 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, |
| | CONNECTING ACCESSIBLE BUILDING OR FACILITY ENTRANCES |
| | WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE |
| | BUILDING OR FACILITY |
| | |
| | 5. ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE GREATER |
| | THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL COMPLY |
| | WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 6. NO ACCESSIBLE PARKING SPACES ARE SHOWN ON THE PLANS |
| | AT THIS STAGE. WHEN SUBMITTED FOR PERMIT, THE MINIMUM |
| | NUMBER OF ACCESSIBLE PARKING SPACES PROVIDED SHALL BE |
| | IN ACCORDANCE WITH SECTION 208.2 OF FLORIDA |
| | ACCESSIBILITY CODE. |
| | |
| | 7. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE, |
| | ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE |
| | SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING |
| | TO AN ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN |
| | OF ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION |
| | 502 OF FLORIDA ACCESSIBILITY CODE |
| | |
| | 8. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, |
| | ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A |
| | PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND |
| | DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA |
| | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 |
| | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 9. ACCESSIBLE PARKING SPACE ACCESS AISLES SHALL BE |
| | LOCATED SO THAT THE USER IS NOT COMPELLED TO WALK OR |
| | WHEEL BEHIND ANOTHER PARKED VEHICLE OR IN THE TRAVEL |
| | LANE. THE ACCESS AISLES SHALL ALSO COMPLY WITH THE |
| | OTHER PROVISIONS OF SECTION OF 502.3 OF FLORIDA |
| | ACCESSIBILITY CODE. |
| | |
| | 10. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 11. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. |
| | |
| | 12. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE |
| | DOES NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL |
| | OPENINGS TO MEET THE DEFINITION OF AN OPEN PARKING |
| | GARAGE, IT WILL BE CONSIDERED AN ENCLOSED PARKING |
| | GARAGE AND MUST HAVE EXHAUST SYSTEMS. THE EXHAUST |
| | SYSTEMS SHALL BE DESIGNED TO MINIMIZE NOISE LEVELS |
| | USING INLINE FAN SILENCERS OR OTHER APPROVED METHODS. |
| | |
| | 13. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 14. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE |
| | ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, |
| | GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: |
| | [email protected] |
| | |
| | 15. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC |
| | PLACES (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION |
| | OF PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, |
| | CONTACT SYBILLE WELTER, ART IN PUBLIC PLACES |
| | COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |