| Date |
Text |
| 2015-09-08 19:13:20 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. SHEET A3.01, ELEVATIONS - BUILDING A. THE AWNINGS |
| | PROPOSED ON THE SOUTH AND WEST ELEVATIONS OF THE |
| | EXISTING BUILDING APPEAR TO HAVE A SUBSTANTIAL |
| | EXTENSION OVER THE SIDEWALK WHICH IS THE RRIGHT-OF-WAY. |
| | PER SECTION 3202.3.1 OF FLORIDA BUILDING CODE, AWNINGS |
| | LOCATED BETWEEN 8 FEET AND 15 FEET ABOVE THE SIDEWALK |
| | SHALL NOT EXTEND MORE THAN TWO-THIRDS THE WIDTH OF THE |
| | SIDE WALK MEASURED FROM THE BUILDING. |
| | |
| | 3. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 4. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. |
| | |
| | 5. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY |
| | CHAPTER 10 OF THE FLORIDA EXISTING BUILDING CODE. THE |
| | HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED |
| | ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT |
| | AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE |
| | PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE |
| | FOR THE TYPE OF CONSTRUCTION USED. |
| | |
| | 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 7. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE |
| | ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, |
| | GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: |
| | [email protected] |
| | |
| | 8. THIS PROJECT MAY BE SUBJECT TO ART IN PUBLIC PLACES |
| | (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF |
| | PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT |
| | SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT |
| | (561) 822-1521, OR BY EMAIL: [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |
Print |