| 2015-08-12 09:39:31 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. SHEET SP-1, SITE PLAN, SHOWS REGULAR PARKING SPACES |
| | THAT ARE CLOSER THAN THE ACCESSIBLE PARKING SPACE TO |
| | THE ENTRANCE OF THE NORTH BUILDING. ALSO, THE PLAN DOES |
| | NOT SHOW AN ACCESSIBLE ROUTE FROM THE ACCESSIBLE |
| | PARKING SPACE TO THE NORTH BUILDING. PER SECTION 208.3 |
| | OF FLORIDA ACCESSIBILITY CODE ACCESSIBLE PARKING SPACES |
| | ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE OF |
| | TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE |
| | FOR EACH BUILDING. THE DESIGN OF ACCESSIBLE PARKING |
| | SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA |
| | ACCESSIBILITY CODE |
| | |
| | 3. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE |
| | |
| | 4. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. |
| | |
| | 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 6. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE |
| | ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, |
| | GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |