Plan Review Notes
Plan Review Notes For Project Z15040039
Project Number Z15040039
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-05-06 15:28:49THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. ALL APARTMENT BUILDINGS SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE, 2012, 5TH EDITION, THE
 DESIGNATION OF "TOWNHOME" FOR FIRE PREVENTION CODE
 PURPOSES WILL BE BASED ON THE FIRE RATING SEPARATION OF
 EACH UNIT.
  
 THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH THE
 NFPA 1, FIRE CODE, 2012 EDITION; FLORIDA FIRE
 PREVENTION CODE, 2012 EDITION, INCLUDING MORE
 SPECIFICALLY, CHAPTER 36, NEW MERCANTILE OCCUPANCY AND
 THE FUEL SERVICE STRUCTURE SHALL COMPLY WITH NFPA 30A
 AUTOMOTIVE AND MARINE SERVICE STATION CODE.
  
 6. FIRE LOAD CALCULATIONS SHALL BE COMPLETED AND
 SUBMITTED TO DETERMINE IF ADDITIONALL WATER SUPPLY , A
 FIRE HYDRAT(S) IS(ARE) NEEDED.
  
 7. BASED ON THE SUBMITTED PLAN AND UNIT FIRE
 SEPARATION, A NFPA 13 COMPLIANT FIRE SPRINKLER SYSTEM
 MAY BE REQUIRED FOR THIS PROJECT.
  
 8. THE LOCATION OF THE GAS METER IS REQUIRED TO BE
 MOVED AWAY FROM AN OF AREA OF POSSIBLE LEAK IGNITION.
 THE GAS METER COULD BE BETTER ISOLATED AWAY FROM THE
 INLINE HOT WATER HEATER AND A/C UNIT SYSTEMS. SHOULD A
 LEAK AT THE METER OCCUR, THOSE IMMEDAITE AREA SOURCES
 CAN TRIGGER AN IGNITION.
  