Plan Review Notes
Plan Review Notes For Project Z15030025
Project Number Z15030025
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2015-04-24 12:25:11AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED APRIL
 17, 2015, FROM JOSH I. LONG, AICP, TO JOHN ROACH,
 PRINCIPAL PLANNER, THE PREVIOUSLY SUBMITTED FIRE
 PREVENTION BUREAU COMMENTS HAVE BEEN ADDRESSED.
  
 HOWEVER, ONE COMMENT NEEDS FURTHER REVIEW REGARDING THE
 LOCATION OF THE FIRE HYDRANT AND FDC AT THE SERVICE
 ROAD. THE BUREAU IS REQUESTING THAT FIRE HYDRANT AND
 FDC BE MOVED CLOSER TO CRANESNEST WAY TO BE USED BY
 FIRE TRUCKS FROM THAT ROADWAY. A FIRE TRUCK WILL NOT BE
 COMMITTED TO THAT DEAD-END ROAD IN THE EVENT OF FIRE
 EMRGENCY.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  