| 2015-08-18 15:41:29 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. THE WHEELCHAIR USER MUST BE ABLE TO OPEN/CLOSE THE |
| | DOOR WHILE ON THE LEVEL LANDING, AND NOT PARTIALLY ON |
| | THE SLOPED PART OF THE RAMP. THEREFORE, FOR THE RAMP |
| | LEADING TO TIJUANA FLATS RESTAURANT, WHEN SUBMITTED FOR |
| | PERMIT, THE PLANS SHALL SHOW THAT THE FRONT EDGE OF THE |
| | TOP LANDING WILL BE MIN. 36 INCHES FROM THE LEADING |
| | EDGE OF THE DOOR SWING, AND THE RAMP MUST BE MIN. 60 |
| | INCHES WIDE, PER FIGURE 404.2.4.1(D) OF FLORIDA |
| | ACCESSIBILITY CODE. |
| | |
| | 3. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE |
| | |
| | 4. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. |
| | |
| | 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SWIMMING POOLS AND SPAS, GAS SYSTEMS, GENERATORS, |
| | FIRE ALARM SYSTEMS, FIRE SPRINKLER AND OTHER FIRE |
| | SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, SITE |
| | LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 6. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, GIS |
| | SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |