2015-03-11 10:36:31DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. FOR ANY BUILDING CROSSING A PROPERTY LINE, EITHER A
 RECORDED UNITY OF TITLE, OR SOME OTHER APPROVED LEGAL
 INSTRUMENT, SHALL BE INCLUDED WITH THE PERMIT
 APPLICATION, OR THE BUILDING MUST HAVE A FIRE WALL
 ALONG THE PROPERTY LINE, PER SECTION 702 OF FLORIDA
 BUILDING CODE, BUILDING, FIRE SEPARATION DISTANCE.
  
 3. DISPERSION OF ACCESSIBLE PARKING SPACES. SHEET SP-1
 CURRENTLY SHOWS REGULAR PARKING SPACES CLOSER TO THE
 ENTRANCES OF THE INDIVIDUAL SHOWROOMS (ROLLS ROYCE,
 BENTLEY, PRSCHE, ETC.) THAN THE ACCESSIBLE PARKING
 SPACES. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE
 ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE
 SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN
 OF ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION
 502 OF FLORIDA ACCESSIBILITY CODE
  
 4. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 5. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 6. IN CASE THE NEW SERVICE BAY BUILDING WILL BE
 CONSIDERED AN ADDITION TO THE EXISTING SERVICE BAY
 BUILDING, THE ADDITION TO THE EXISTING BUILDING IS
 COVERED BY CHAPTER 10 OF THE FLORIDA EXISTING BUILDING
 CODE. THE HEIGHT AND/OR AREA INCREASE DUE TO THE
 PROPOSED ADDITION SHALL NOT INCREASE THE TOTAL BUILDING
 HEIGHT AND/OR AREA BEYOND THAT ALLOWED UNDER THE
 APPLICABLE PROVISIONS OF CHAPTER 5 OF THE FLORIDA
 BUILDING CODE FOR THE TYPE OF CONSTRUCTION USED.
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SWIMMING POOLS AND SPAS, GAS SYSTEMS, GENERATORS,
 FIRE ALARM SYSTEMS, FIRE SPRINKLER AND OTHER FIRE
 SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, SITE
 LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 8. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, GIS
 SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  