| 2015-03-11 10:36:31 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. FOR ANY BUILDING CROSSING A PROPERTY LINE, EITHER A |
| | RECORDED UNITY OF TITLE, OR SOME OTHER APPROVED LEGAL |
| | INSTRUMENT, SHALL BE INCLUDED WITH THE PERMIT |
| | APPLICATION, OR THE BUILDING MUST HAVE A FIRE WALL |
| | ALONG THE PROPERTY LINE, PER SECTION 702 OF FLORIDA |
| | BUILDING CODE, BUILDING, FIRE SEPARATION DISTANCE. |
| | |
| | 3. DISPERSION OF ACCESSIBLE PARKING SPACES. SHEET SP-1 |
| | CURRENTLY SHOWS REGULAR PARKING SPACES CLOSER TO THE |
| | ENTRANCES OF THE INDIVIDUAL SHOWROOMS (ROLLS ROYCE, |
| | BENTLEY, PRSCHE, ETC.) THAN THE ACCESSIBLE PARKING |
| | SPACES. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE |
| | ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE |
| | SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING |
| | TO AN ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN |
| | OF ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION |
| | 502 OF FLORIDA ACCESSIBILITY CODE |
| | |
| | 4. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE |
| | |
| | 5. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. |
| | |
| | 6. IN CASE THE NEW SERVICE BAY BUILDING WILL BE |
| | CONSIDERED AN ADDITION TO THE EXISTING SERVICE BAY |
| | BUILDING, THE ADDITION TO THE EXISTING BUILDING IS |
| | COVERED BY CHAPTER 10 OF THE FLORIDA EXISTING BUILDING |
| | CODE. THE HEIGHT AND/OR AREA INCREASE DUE TO THE |
| | PROPOSED ADDITION SHALL NOT INCREASE THE TOTAL BUILDING |
| | HEIGHT AND/OR AREA BEYOND THAT ALLOWED UNDER THE |
| | APPLICABLE PROVISIONS OF CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE FOR THE TYPE OF CONSTRUCTION USED. |
| | |
| | 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SWIMMING POOLS AND SPAS, GAS SYSTEMS, GENERATORS, |
| | FIRE ALARM SYSTEMS, FIRE SPRINKLER AND OTHER FIRE |
| | SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, SITE |
| | LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 8. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, GIS |
| | SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |