| Date |
Text |
| 2015-02-04 13:29:52 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 2. ALL LIFE SAFETY SYSTEMS IN THE BUILDING SHALL REMIAN |
| | FULLY FUNCTIONAL DURING ALL TIMES OF CONSTRUCTION. |
| | |
| | 3. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF |
| | THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE |
| | AND COMPLIANCE. |
| | |
| | 4. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | |
| | 5. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE |
| | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP |
| | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | 6. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | 7. THE CONSTRUCTION SHALL MEET OR EXCEED THE EXISTING |
| | FIRE PREVENTION FEATURES OF THE BUILDING AND COMPLY |
| | WITH ALL APPLICABLE CODES AND STANDARDS OF THE STATE OF |
| | FLORIDA, INCLUDING BUT NOT LIMITED TO, NFPA 101, |
| | FLORIDA 2012 EDITION, CHAPTER 18, NEW HEALTHCARE |
| | OCCUPANCIES. |
| | |
| | 8. ALL EXISTING EXIT IDENTIFICATION, EXIT ACCESS AND |
| | EXIT TO A PUBLIC WAY SHALL NOT BE COMPROMISED OR |
| | BLOCKED AT ANY TIME AND THEY SHALL BE MAINTAINED OPEN |
| | AND CLEAR AT ALL TIMES DURING THE CONSTRUCTION PERIOD. |
| | |
| | 9. A LIFE SAFETY PLAN SHALL BE PROVIDED AT THE TIME OF |
| | BUILDING SUBMITTAL THAT SHOWS OCCUPANCY LOADS, COMMON |
| | PATHS OF TRAVEL, EXIT ACCESS, EXIT CORRIDORS AND ALL |
| | EXIT DOOR LOCATIONS. EMERGENCY LIGHTS AND FIRE |
| | EXTINGUISHER LOCATIONS SHALL BE INDICATED. |
| | |
| | |
| |
Print |