Plan Review Notes
Plan Review Notes For Project Z15010007
Project Number Z15010007
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-02-04 14:01:30THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. ALL APARTMENT BUILDINGS SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE, 2012 EDITION, INCLUDING
 MORE SPECIFICALLY, CHAPTER 30, NEW APARTMENTS.
  
 6. THE DESIGNATION OR TERM OF TOWNHOME AND THE
 REQUIREMENT OF FIRE SPRINKLERS WILL BE DETERMINED BY
 THE FIRE PREVENTION CONSTRUCTION FEATURES OF UNIT
 SEPARATION.
  
 7. THE LOCATION OF FIRE HYDRANTS WILL BE CONSISTENT
 WITH PHASE I.
  
 8. ALL UNDERGROUND WATER LINES CONNECTED TO A FIRE
 HYDRANT SHALL BE CONSIDERED A FIRE LINE. THE FIRE LINE
 SHALL BE PROPERLY PERMITTED AND SHALL BE INSPECTED BY A
 FIRE INSPECTOR AND OTHER APPROPRIATE CITY INSPECTORS
 PRIOR TO BEING COVERED OVER.
  