Plan Review Notes
Plan Review Notes For Project Z14120035
Project Number Z14120035
Review Stop STORM
Sequence Number 1
Notes
Date Text
2015-01-13 13:36:001. PLOT SITE PLAN (SP-1.0) AT USABLE SCALE. CHECK SCALE
 BAR.
  
 2. ELEVATIONS NEED TO REFERENCE NGVD 1929 (SHEETS
 C3.01, C4.01).
  
 3. CAN ADA RAMP BE LOCATED CLOSER TO THE CORNER?
  
 4. SHOW UTILITIES ON THE ELECTRICAL PLANS.
  
 5. IS THERE A CONNECTION TO AN OFFSITE DRAINAGE SYSTEM?
  
 6. UPDATED FEMA FLOOD INSURANCE RATE MAPS (DRAFT
 VERSION) ARE AVAILABLE.
  
 7. SWPPP EROSION AND SEDIMENT CONTROL PLAN WILL BE
 REQUIRED WITH THE ENGINEERING PERMIT SUBMITTAL.
  
 8. NPDES CONSTRUCTION PERMIT REQUIRED BEFORE START OF
 CONSTRUCTION.
  
 9. PROVIDE WITH THE ENGINEERING PERMIT SUBMITTAL S&S
 CALCULATIONS DEMONSTATING THE STORNMWATER MANAGEMENT
 SYSTEM MEETS SFWMD CRITERIA FOR WATER QUALITY
 TREATMENT.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 PUBLIC WORKS DEPARTMENT
 [email protected]
 561-494-1120
  