| Date |
Text |
| 2015-01-13 21:43:37 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. NUMBER OF ACCESSIBLE PARKING SPACES. PLAN SHEETS |
| | A210 AND A211 SHOWS THAT 6 ACCESSIBLE PARKING SPACES |
| | ARE PROPOSED OUT OF A TOTAL 357 PARKING SPACES. PER |
| | TABLE 208.2 OF FLORIDA ACCESSIBILITY CODE, FOR PARKING |
| | FACILITIES WITH BETWEEN 301 AND 400 PARKING SPACES, 8 |
| | ACCESSIBLE PARKING SPACES ARE TO BE PROVIDED. |
| | |
| | 3. ACCESSIBLE ROUTE FROM ACCESSIBLE PARKING SPACE. PLAN |
| | SHEETS A210 SHOWS THE NORTH ACCESSIBLE PARKING SPACE ON |
| | THE GROUND LEVEL WITH AN ACCESSIBLE ROUTE THAT FORCES |
| | THE USER TO ENTER THE VEHICLE TRAVEL LANE AND PASS |
| | BEHIND ANOTHER PARKED VEHICLE. PER SECTION 208.3 OF |
| | FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES |
| | ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE OF |
| | TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE |
| | FOR EACH BUILDING AND SERVED BY AN ACCESSIBLE ROUTE |
| | THAT DOES NOT COMPEL THE USER TO PASS BEHIND ANOTHER |
| | PARKED VEHICLE. |
| | |
| | 4. VAN ACCESSIBLE PARKING SPACES. PER SECTION 208.2.4 |
| | OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX |
| | ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING |
| | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN |
| | ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY |
| | CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT |
| | SPACE AND VEHICULAR ACCESS ROUTE). AS 8 ACCESSIBLE |
| | PARKING SPACES ARE REQUIRED, 2 VAN ACCESSIBLE SPACES |
| | ARE TO BE PROVIDED. |
| | |
| | 5. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 6. FOR STREET ADDRESSING CONTACT MICHAEL ORIO, GIS |
| | SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |
Print |