2015-03-18 20:28:07PB 950QQQQ - 1ST RESUBMITTAL 2/25/15
 PALM BEACH COUNTY CONVENTION CENTER GARAGE
 650 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 THIS SET OF INTERIM COMMENTS IS BEING ISSUED TO ALLOW
 THE DESIGN TEAM TO ADDRESS SOME OF THE DEFICIENCIES
 WHILE STAFF CONTINUES TO ANALYZE THE APPLICANT'S
 2/25/15 RESPONSES TO THE COMMENTS LISTED AS "STILL
 UNDER STAFF REVIEW". THE "REVISED COMMENT" CATEGORY
 REQUIRES ADDITIONAL FOLLOW UP INFORMATION BASED ON THE
 REVISED PLANS AND THE "NEW COMMENT" CATEGORY IS A
 RESULT OF CHANGES MADE TO THE ORIGINAL PLANS. THE
 "CONDITION" COMMENTS WILL BE ADDED AS PART OF THE
 ULTIMATE APPROVAL LETTER. THE "REPEAT COMMENTS" WERE
 NOT SUFFICIENTLY ADDRESSED.
  
 GENERAL
  
 1) CONDITION: STAFF HAS SPOKEN WITH RELATED REGARDING
 THE AREA SOUTH OF THE HOTEL LOADING ZONE THAT IS
 CURRENTLY NOT INCLUDED ON EITHER THE HOTEL SITE PLAN OR
 THIS SITE PLAN. RELATED HAS AGREED TO SUPPLY PLANS FOR
 THE MISSING PIECE ONCE THIS GARAGE APPLICATION IS
 APPROVED, SO THEY CAN INTEGRATE THEIR PLANS WITH THE
 APPROVED GARAGE DESIGN. RELATED HAS STATED THEY WILL
 CONSTRUCT THE LOADING AREA CHANGES IF THE GARAGE IS
 UNDER CONSTRUCTION BEFORE THEY HAVE COMPLETED THE HOTEL
 CONSTRUCTION. IF THE HOTEL IS COMPLETED AND THE GARAGE
 CONSTRUCTION HAS NOT BEGUN, THE LOADING ZONE
 MODIFICATION CONSTRUCTION WILL BE BORNE BY THE COUNTY
 AS PART OF THE GARAGE CONSTRUCTION. THIS CONDITION WILL
 APPLY TO BOTH APPROVALS.
  
 2) REPEAT COMMENT: PLEASE PROVIDE DETAILS ON HOW THE
 PROPOSED GARAGE COMPLIES WITH THE EXHIBIT D "ENERGY
 SAVING METHODS" OF THE CITYPLACE DRI. - THE RESPONSE
 SHALL LIST THE SPECIFIC ITEMS IN EXHIBIT D THAT WILL BE
 USED AND WHY OTHERS ARE NOT BEING IMPLEMENTED.
  
 SITE PLAN
  
 3) REVISED COMMENT: THE SITE DATA TABLE WAS UPDATED TO
 INCLUDE THE ENTIRE CONVENTION CENTER PARCEL. THE AMOUNT
 OF LANDSCAPE AREA APPROVED BY RES. NO. 44-99 WAS
 15.03%. THE PROPOSED OVERALL CONVENTION CENTER SITE
 ONLY HAS 13.6% LANDSCAPE. PROVIDE THE ADDITIONAL
 LANDSCAPE AREA.
  
 4) REVISED COMMENT: PROVIDE A PARKING MANAGEMENT PLAN
 THAT CONSOLIDATES THE APPLICANT RESPONSES INCLUDED WITH
 ITEMS 8 A THROUGH G IN ONE CENTRAL DOCUMENT THAT WILL
 BE INCLUDED WITH THE ULTIMATE APPROVAL LETTER.
  
 5) STILL UNDER STAFF REVIEW: THE APPROVED PHASE 2 PLAN
 SHOWS APPROXIMATELY 110 FEET OF THE FLORIDA AVENUE
 FRONTAGE INTERRUPTED BY VEHICULAR ACCESS POINTS. THE
 PROPOSED PLAN EXPANDS THIS TO APPROXIMATELY 140 FEET
 (NOT INCLUDING THE STABILIZED FIRE DEPARTMENT ACCESS
 ROADWAY). THERE HAS BEEN NO JUSTIFICATION PROVIDED TO
 CHANGE THE CONDITIONS OF THE CURRENT APPROVAL TO
 SUPPORT THIS ENLARGEMENT OF THE DRIVEWAYS ALONG THE
 FRONTAGE AREA.
  
 7) REVISED COMMENT: THE TURNING RADIUS DRAWINGS FOR
 FIRE DEPARTMENT ACCESS ROADWAY DO NOT INCLUDE THE
 EXISTING TREES. IT APPEARS THAT THERE IS AT LEAST ONE
 TREE THAT WILL BE HIT BY A TRUCK NEGOTIATING THE
 SOUTHEAST CURVE.
  
 8) NEW COMMENT: THE RECONFIGURED FIRE DEPARTMENT ACCESS
 ROADWAY IS SHOWN CROSSING TRACT 7. TRACT 7 IS NOT UNDER
 OWNERSHIP OF PALM BEACH COUNTY, BUT RATHER THE
 COMMUNITY REDEVELOPMENT AGENCY AND MAY NOT BE USED AS
 PART OF THE PLANS APPROVED BY A MINOR AMENDMENT. TRACT
 7 INCLUDES LANDSCAPE TO BUFFER THE REAR OF THE BUFFER
 TOWNHOUSES THAT MAY NOT BE REMOVED AS PART OF THE
 GARAGE PROJECT. PLEASE NOTE THAT THE RESTRICTIVE
 COVENANT REQUIRED AS PART OF CRA RESOLUTION 99-10 ONLY
 PERMITS TRACT 7 TO BE USED FOR LANDSCAPE, HARDSCAPE,
 UNDERGROUND UTILITIES AND PEDESTRIAN ACCESS. ROADWAYS
 ARE PROHIBITED.
  
 9) STILL UNDER STAFF REVIEW: A SIDEWALK SHALL BE
 PROVIDED ON THE WEST SIDE OF FLORIDA AVENUE TO CONNECT
 THE SIDEWALK IN FRONT OF THE HOTEL TO THE EXISTING
 SIDEWALK ON THE NORTH SIDE OF THE TOWNHOUSES. THIS
 SIDEWALK SHALL INCLUDE APPROPRIATE PEDESTRIAN LIGHTING.
  
 10) NEW COMMENT: IF THE SIDEWALK IS ONLY SUPPLIED ON
 THE EAST SIDE OF FLORIDA AVENUE, THEN THE COUNTY SHALL
 BE RESPONSIBLE FOR REMOVING THE STRETCH OF SIDEWALK
 THAT WILL NO LONGER SERVE A PURPOSE IN THE RIGHT-OF-WAY
 NORTH OF TRACT 7. THIS IS NOT UNIFORMLY SHOWN ON ALL
 THE PLANS.
  
 11) CONDITION: PLEASE NOTE THAT ALL LIGHT POLES AND
 FIXTURES IN THE ENTRY AREA SHALL MATCH THE STYLE BEING
 INSTALLED BY THE HOTEL.
  
 12) CONDITION: THE DRI REQUIRES THE SUBMITTAL OF A
 SIGNAGE PROGRAM FOR ANY NEW SIGNS. THE SIGNAGE PROGRAM
 SHALL BE SUBMITTED FOR REVIEW AS A MINOR PLANNED
 DEVELOPMENT AMENDMENT PRIOR TO THE SIGNAGE FOR THE
 CONVENTION CENTER GARAGE REVIEW AS PART OF A BUILDING
 PERMIT.
  
 13) STILL UNDER STAFF REVIEW: THE STAFF HAS DETERMINED
 THAT THE CURRENT PLANS DO NOT SHOW COMPLIANCE WITH THE
 REQUIREMENT THAT ROOFTOP PARKING SPACES BE SCREENED.
 PLEASE PROVIDE INFORMATION ON HOW COMPLIANCE WITH THIS
 REQUIREMENT WILL BE ACHIEVED.
  
 14) NEW COMMENT: DUE TO THE PROVISION OF COVERED
 PARKING SPACES ON THE ROOF, THERE NEED TO BE AT LEAST
 ADA SPACES THAT ARE COVERED. PLEASE CONTACT ROBERT
 BROWN, CHIEF BUILDING OFFICIAL, DIRECTLY FOR FURTHER
 DETAILS.
  
 15) NEW COMMENT: PLEASE DESCRIBE WHAT THE DIAMOND
 SHAPES ARE THAT ARE SHOWN SURROUNDING THE SUPPORT
 COLUMNS. IF THESE EXTEND ABOVE THE HEIGHT OF THE WHEEL
 STOPS, THEN SOME, TO INCLUDE ONES AT THE HEAD OF THE
 ADA SPACES MAKE THOSE SPACES NON-FUNCTIONING FOR
 PARKING (INSUFFICIENT DEPTH).
  
 16) REVISED COMMENT: THANK YOU FOR PROVIDING THE
 REQUIRED/PROVIDED NUMBER OF BICYCLE PARKING SPACES FOR
 THE SITE. PLEASE PROVIDE THE LOCATIONS AND NUMBER OF
 THE EXISTING BICYCLE PARKING SPACES SO THAT STAFF CAN
 VERIFY THAT THE DISTRIBUTION ADEQUATELY SERVES THE
 SITE. THE NEW SPACES ON THE WEST SIDE OF THE GARAGE ARE
 NOT READILY VISIBLE TO THE BICYCLE USER. SOME OF THE
 SPACES SHOULD BE MOVED TO THE WESTERN EDGE OF THE PLAZA
 AREA AT THE CONVENTION CENTER ENTRANCE TO BE MORE
 VISIBLE.
  
 17) NEW COMMENT: SHOW HOW THE 19 BICYCLE RACKS WILL BE
 ALIGNED IN THE WESTERN BUILDING LOCATION BY THE LOADING
 DOCKS. THIS INCLUDES THE CORRECT BICYCLE PAD
 DIMENSIONS. PLEASE REMEMBER THAT A MINIMUM OF TWO (2)
 FEET ARE REQUIRED AT THE END OF THE ROW WHEN AGAINST A
 FIXED OBJECT SUCH AS A WALL.
  
 18) CONDITION: INTERNAL SIGNAGE SHALL BE INSTALLED TO
 GUIDE USERS TO THE ELEVATORS AND STAIRWELLS AT THE
 NORTHWEST CORNER OF THE GARAGE. THE REMAINING
 STAIRWELLS SHALL BE SIGNED AS EMERGENCY EGRESS ONLY.
  
 19) STILL UNDER STAFF REVIEW: THE EVENT STAGING AREA
 SHALL BE SEPARATED FROM THE WESTERN GARAGE EXIT LANES
 BY A LANDSCAPE BUFFER AND IT SHALL BE BROKEN UP BY THE
 PLACEMENT OF INTERNAL LANDSCAPE. THE BUFFER WILL SERVE
 TO VISUALLY SCREEN THE STAGING AREA FROM THE GARAGE
 PATRONS. ADDITIONALLY THE BUFFER AND THE INTERNAL
 LANDSCAPE WILL BREAK UP THE LARGE EXPANSE OF PAVING AT
 THE STAGING AREA IN ACCORDANCE WITH THE DRI REQUIREMENT
 TO "REDUCE COVERAGE BY ASPHALT, CONCRETE, ROCK, AND
 SIMILAR SUBSTANCES IN STREETS, PARKING LOTS, AND OTHER
 AREAS TO REDUCE LOCAL AIR TEMPERATURES AND REFLECT
 LIGHT AND HEAT."
  
 20) NEW COMMENT: THE APPLICANT'S RESPONSE STATES THAT
 ONLY ONE STATIC EXIT LANE WILL BE PROVIDED AT THE
 NORTHEAST CORNER OF THE GARAGE; HOWEVER, THIS IS NOT
 VERIFIED BY THE STRIPING PLAN, WHICH DOES NOT INCLUDE
 PAVEMENT MARKINGS TO GUIDE A DRIVER TO THE SINGLE EXIT
 LANE.
  
 LANDSCAPE
  
 21) STILL UNDER STAFF REVIEW: THE APPROVED PLAN
 REQUIRES PLANTER BOXES 42 INCHES ABOVE EACH PARKING
 DECK TO BREAK UP THE FACADE OF THE GARAGE. PLEASE
 PROVIDE JUSTIFICATION AS TO WHY NOT PROVIDING THE
 PLANTER BOXES IS NOT A CHANGED CONDITION OF APPROVAL,
 WHICH WOULD NECESSITATE A REVIEW OF THE GARAGE BY THE
 CITY COMMISSION.
  
 22) NEW COMMENT: THE TOTAL SITE AREA LISTED ON SHEET
 AS000 IS 848,549 SQ. FT., BUT THE TOTAL SITE AREA
 LISTED ON SHEET LD-4 OF 4 IS 841,373. WHICH IS CORRECT?
 ALL DATA CALCULATIONS SHALL BE BASED ON ACCURATE
 NUMBERS.
  
 23) REVISED COMMENT: THE EAST PROPERTY CONTAINS 17, NOT
 16 PROVIDED TREES. PLEASE UPDATE THE TABLE.
  
 24) STILL UNDER STAFF REVIEW: THE CONVENTION CENTER HAS
 NOT MAINTAINED ITS PARKING LOT TREES SINCE THEY WERE
 ORIGINALLY INSTALLED AS EVIDENCED BY THE MANY PARKING
 LOT ISLANDS WITHOUT TREES. THESE MISSING TREES ARE
 STILL REQUIRED TO BE MITIGATED AS PART OF THE TREE
 ALTERATION PERMIT. A TABLE VERIFYING THAT ALL OF THE
 REMOVED TREES HAVE BEEN MITIGATED IS REQUIRED AS PART
 OF THE TREE ALTERATION PERMIT. PLEASE NOTE THAT THERE
 WAS NOT INFORMATION PROVIDED AS TO THE CANOPY SIZE OF
 ANY OF THE TREES PROPOSED FOR REMOVAL. DO ANY OF THESE
 TREES HAVE GREATER THAN 35 FEET OF CANOPY?
  
 ELEVATION
  
 25) REVISED COMMENT: THE FINAL COLOR ELEVATIONS THAT
 INCORPORATE THE NEIGHBORHOOD COMMENTS WERE NOT
 PROVIDED.
  
 26) REPEAT COMMENT: PROVIDE A LINE OF SIGHT DRAWING
 NORTH ALONG GEORGIA AVENUE FROM SOUTH OF O STREET.
  
 27) NEW COMMENT: THE SOUTH AND WEST ELEVATION DRAWINGS
 CALL OUT THE FIRE DEPARTMENT ACCESS ROADWAY GATE AS
 GALVANIZED, NOT COATED, CHAIN LINK AS IS SHOWN ON THE
 SITE PLANS.
  
 28) NEW COMMENT: THE EAST ELEVATION DRAWING CALLS OUT A
 DIGITAL MONUMENT SIGN. THIS SHALL BE REMOVED FROM THE
 PLAN.
  
 29) NEW COMMENT: WHY DOES THE NORTH/SOUTH BUILDING
 SECTION SHOW BICYCLE RACKS IN THE BUILDING?
  