Plan Review Notes
Plan Review Notes For Project Z14110031
Project Number Z14110031
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-12-04 16:46:41THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE HOTEL STRUCTURE SHALL COMPLY WITH THE CURRENT
 EDITIONS OF THE FLORIDA FIRE PREVENTION CODE, THE NFPA
 LIFE SAFETY CODE, INCLUDING MORE SPECIFICALLY, CHAPTER
 28, HOTELS AND DORMITORES.
  
 5. THE ECO-VILLAS SHALL COMPLY WITH THE CURRENT
 EDITIONS OF THE FLORIDA FIRE PREVENTION CODE, THE NFPA
 LIFE SAFETY CODE, INCLUDING MORE SPECIFICALLY, CHAPTER
 30, NEW APARTMENTS.
  
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH THE CURRENT
 EDITION OF THE FLORIDA FIRE PREVENTION CODE, CHAPTER 42
 STORAGE OCCUPANCIES (PARKING STRUCTURES), AND NFPA 88A,
 PARKING STRUCTURES,
  
 7. THE CLUBHOUSE SHALL COMPLY THE CURRENT EDITIONS OF
 THE FLORIDA FIRE PREVENTION CODE, THE NFPA LIFE SAFETY
 CODE, INCLUDING MORE SPECIFICALLY, CHAPTER 12, NEW
 ASSEMBLY OCCUPANCIES AND CHAPTER 42 STORAGE OCCUPANCIES
 (PARKING STRUCTURES).
  
 8. THE RESTAURANT SHALL COMPLY THE CURRENT EDITIONS OF
 THE FLORIDA FIRE PREVENTION CODE, THE NFPA LIFE SAFETY
 CODE, INCLUDING MORE SPECIFICALLY, CHAPTER 12, NEW
 ASSEMBLY OCCUPANCIES.
  
 9. THE TENNIS SHOP APPAERS TO BE A MIXED OCCUPANCY AND
 SHALL BE IDENTIFIED AS TO THE PROPOSED STRICTIST
 OCCUPANCY OF COMPLIANCE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGECNY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 12. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 13. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE
 ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED
 ON THE PLAN.
  
 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR EACH
 STRUCTURE.
  
 15. ANY GATES SHALL BE EQUIPPED WITH A KNOX KEY SWITCH
 SYSTEM.
  
 16. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED
 FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 17. ALL COMMERCIAL KITCHEN EQUIPMENT AND OPERATIONS
 SHALL COMPLY WITH NFPA 96, STANDARD FOR VENTILATION
 CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING
 OPERATIONS. EXTINGUISHMENT AND VENTILATION SYSTEM SHOP
 DRAWINGS SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 18. NO EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE.
 ANY AND ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH
 CHAPTER 7 OF THE FLORIDA FIRE PREVENTION CODE AND
 PRE-APPROVED (PRIOR TO INSTALLATION) BY THE BUREAU OF
 FIRE PREVENTION. CLOSE COORDINATION WITH THE BUREAU OF
 FIRE PREVENTION IS STRONGLY ENCOURAGED TO AVOID
 MISUNDERSTANDINGS, MISINTERPRETATIONS AND DELAYS
 RELATED TO EGRESS REQUIREMENTS.
  