Plan Review Notes
Plan Review Notes For Project Z14110031
Project Number Z14110031
Review Stop B
Sequence Number 1
Notes
Date Text
2014-12-10 12:25:35DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. PLEASE SHOW ACCESSIBLE PARKING SPACE PROVISION FOR
 THE ECO-VILLAS. ALSO, PLEASE PROVIDE A COUNT OF
 ACCESSIBLE PARKING SPACES FOR EACH PARKING LOT AND THE
 TWO PHASES OF THE PARKING STRUCTURE. PER SECTION 208.3
 OF FLORIDA ACCESSIBILITY CODE ACCESSIBLE PARKING SPACES
 ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE OF
 TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE
 FOR EACH BUILDING. THE DESIGN OF ACCESSIBLE PARKING
 SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA
 ACCESSIBILITY CODE
  
 3. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE,
 ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A
 PARKING STRUCTURE, SHALL BE "VAN ACCESSIBLE" AND
 DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA
 ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98
 INCHES AT SPACE AND VEHICULAR ACCESS ROUTE)
  
 4. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE.
  
 5. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED. THE
 EQUIVALENT REQUIREMENTS FOR THE SINGLE-FAMILY DWELLINGS
 ARE IN SECTION R302 OF FLORIDA BUILDING CODE
 (RESIDENTIAL).
  
 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 7. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE
 OBTAINED BEFORE COMMENCING THE WORK. SEPARATE PERMITS,
 PLANS AND FEES, ARE REQUIRED FOR SWIMMING POOLS AND
 SPAS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, FIRE
 SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, GREASE
 INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, SITE
 IRRIGATION, ETC.
  
 14. FOR STREET ADDRESSING CONTACT MICHAEL ORIO, GIS
 SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  