Plan Review Notes
Plan Review Notes For Project Z14100025
Project Number Z14100025
Review Stop STORM
Sequence Number 1
Notes
Date Text
2014-11-10 10:34:481. PROVIDE DRAINAGE CALCULATIONS DEMONSTATING EACH
 DRAINAGE SUB-BASIN DRAINING TO EXFILTRATION TRENCH OR
 DRY DETENTION BASIN HAS SUFFICIENT WATER QUALITY
 TREATMENT STORAGE AND PEAK FLOW ATTENUATION.
  
 2. PROVIDE DETAILS OF THE EXFILTRATION TRENCHES AND
 CONTROL STRUCTURES.
  
 3. APPARENT CONFLICT BETWEEN LIGHTPOLE AND EXFILTRATION
 TRENCH LOCATED APPROXIMATELY 125 FEET SOUTH OF THE
 MATCHLINE ON SHEET C3.00
  
 4. SHOW LOCATION OF R/W LINE ON FLAGLER DRIVE TYPICAL
 SWALE SECTION ON SHEET C3.01.
  
 5. CONSIDER CONSTRUCTING A BERM BETWEEN SIDEWALK AND
 SWALE TO INCREASE STORAGE IN SWALE BEFORE SPILLING OVER
 THE SIDEWALK.
  
 6. MANHOLE/INLET SYMBOLS IN PAVING, GRADING AND
 DRAINAGE LEGEND (SHEET C3.00) DO NOT MATCH PLAN
 SYMBOLS.
  
 7. SFWMD PERMIT TO BE OBTAINED/MODIFED BEFORE START OF
 CONSTRUCTION.
  
 8. NPDES PERMIT TO BE OBTAINED BEFORE START OF
 CONSTRUCTION.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING AND PUBLIC WORKS DEPT.
 561-494-1120