Plan Review Notes
Plan Review Notes For Project Z14090017
Project Number Z14090017
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-10-07 11:13:43THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. PAY CLOSE ATTENTION TO THE SEPARATION
 DIMENSIONS OF ANY CONSTRUCTION TRAILERS AS FIRE
 SPRINKLERS MAY BE REQUIRED.
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
 5. ALL APARTMENT BUILDINGS SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE, 2010 EDITION, THE LIFE
 SAFETY CODE, 2009 EDITION, INCLUDING MORE SPECIFICALLY,
 CHAPTER 30, NEW APARTMENTS.
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
 7. THE SEPARATION AND OPENING PROTECTION BETWEEN THE
 PARKING GARAGE AND HOTEL SHALL BE IN ACCORDANCE AND
 COMPLIANCE WITH THE SPECIFIC AND MOST STRINGENT
 PROVISION REQUIREMENT OF EITHER CHAPTER.
 8. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE, INCLUDING THE PARKING GARAGE. TEMPORARY
 STANDPIPES ARE REQUIRED WHEN THE BUILDING REACHES THREE
 LEVELS OR THIRTY FEET WHILE BEING CONSTRUCTED. SEPARATE
 SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED
 AND APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
 9. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
 10. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY
 EQUIPMENT.
 11. OCCUPANT LOADS FOR ALL SPACES SHALL BE DETERMINED
 AND SUBMITTED WITH THE SUBMITTED PLAN AND WHEN APPROVED
 THEY ARE REQUIRED TO BE POSTED WHERE APPLICABLE.
 12. THE FIRE RATING OF ALL SHAFTS SHALL BE CLEARLY
 INDICATED ON THE BUILDING PLAN.
 13. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
 14. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
 15. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE
 ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED
 ON THE PLAN.
 16. ALL EXIT DISCHARGE LOCATIONS SHALL BE CLEARLY
 ILLUSTRATED ON THE PLAN.
 17. ALL ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING
 EQUIPMENT SHALL BE ILLUSTRATED ON THE PLAN.
  
 18. ALL PORTABLE FIRE EXTINGUISHERS LOCATIONS SHALL BE
 CLEARLY IDENTIFIED AND INDICATED ON THE PLAN.
  
 19. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 20. OFF STREET ACCESS TO THE FIRE PUMP ROOM IS
 REQUIRED. THE LOCATION OF THE DOOR INSIDE THE GARAGE
 AREA IS NOT APPROVED.
  
 21. BOTH STAIRWELLS OF THE PARKING GARAGE APPEAR TO BE
 UNPROTECTED. NO DOOR IS SHOWN AT THE STAIRWELL
 ENTRANCE.
  
 22. THE VESTIBULE DOOR AREAS OF THE PARKING GARAGE AREA
 SHALL BE PROTECTED FROM VEHICULAR TRAFFIC WITH
 BOLLARDS.
  
 23. THE VESTIBULE ON THE THIRD FLOOR OF THE PARKING
 GARAGE DOES NOT SHOW DOORS.
  
 24. ALL UNDERGROUND FIRE LINE WORK REQUIRES AN
 INSPECTION BY THE BUREAU OF FIRE PREVENTION.
  