2014-10-07 18:13:58DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. THE PROPOSED BUILDING WILL BE IN FLOOD ZONE AE. THE
 ELEVATION OF THE FIRST FLOOR OF THE BUILDING AND ALL
 ASSOCIATED MECHANICAL EQUIPMENT (CHILLERS, GENERATORS
 ETC.) SHALL BE 6 INCHES (FREEBOARD) ABOVE BASE FLOOD
 ELEVATION.
  
 3. PARKING GARAGE STAIRWELLS. ON SHEETS A2.02 AND A2.04
 THE TWO PARKING GARAGE STAIRWELLS ARE CURRENTLY SHOWN
 WITH NO DOORS TO PROTECT THE STAIRWELLS AT THE 2ND AND
 3RD FLOORS.
  
 4. PARKING GARAGE ELEVATOR VESTIBULE. ON SHEET A2.04
 THE 3RD FLOOR ELEVATOR VESTIBULE IS CURRENTLY SHOWN
 WITH NO DOORS TO PROTECT THE ELEVATOR SHAFT.
  
 5. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 6. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 7. IF THE PARKING GARAGE DOES NOT HAVE WALL OPENINGS,
 OR SUFFICIENT WALL OPENINGS TO MEET THE DEFINITION OF
 AN OPEN PARKING GARAGE, IT WILL BE CONSIDERED AN
 ENCLOSED PARKING GARAGE AND MUST HAVE EXHAUST SYSTEMS.
 THE EXHAUST SYSTEMS SHALL BE DESIGNED TO MINIMIZE NOISE
 LEVELS USING INLINE FAN SILENCERS OR OTHER APPROVED
 METHODS.
  
 8. ALL APPLICABLE PERMITS AND SUB-PERMITS MUST BE
 OBTAINED BEFORE COMMENCING THE WORK. SEPARATE PERMITS,
 PLANS AND FEES, ARE REQUIRED FOR SWIMMING POOLS AND
 SPAS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, FIRE
 SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, GREASE
 INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, SITE
 IRRIGATION, ETC.
  
 BUILDING OFFICIAL