| Date |
Text |
| 2014-10-06 14:44:08 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. THE BUILDING ADDRESSES SHALL BE CLEARLY VISIBLE FROM |
| | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE |
| | DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF |
| | POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. ALL APARTMENT BUILDINGS SHALL COMPLY WITH THE |
| | FLORIDA FIRE PREVENTION CODE, 2010 EDITION, THE LIFE |
| | SAFETY CODE, 2009 EDITION, INCLUDING MORE SPECIFICALLY, |
| | CHAPTER 30, NEW APARTMENTS. THE DESIGNATION OF A |
| | TOWNHOME NOT REQUIRING THE ABOVE SHALL BE REVIEWED |
| | THROUGH FURTHER BUILDING DESIGN AND TENANT SEPARATIONS. |
| | |
| | 6. THE CLUBHOUSE AND OTHER COMMON AREAS SHALL BE |
| | SUBJECT TO ANNUAL FIRE INSPECTIONS. |
| | |
| | 7. AT THE CULBHOUSE, BASED ON ROOF DESIGN, NOTICE IS |
| | REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY |
| | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE |
| | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE |
| | PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY |
| | DOOR. |
| | |
| | 8. ALL UNDERGROUND FIRE LINE INSTALLATIONS TO FIRE |
| | HYDRANTS AND/OR FIRE SPRINKLER SYSTEMS SHALL BE |
| | SUBMITTED FOR PERMIT AND INSPECTED BY THE FIRE |
| | PREVENTION BUREAU'S FIRE INSPECTORS. |
| | |
| | 9. FIRE HYDRANT LOCATIONS SHALL BE APPROVED IN PART |
| | THROUGH THE FIRE PREVENTION BUREAU AT A MINIMUM OF 300' |
| | SEPARATION. |
| | |
| | 10. GATE ACCESS POINTS SHALL BE EQUIPPED WITH A KNOX |
| | KEY SWITCH FOR 24HR EMERGENCY ACCESS. THE GATE SHALL |
| | OPEN WITH A MINIMUM FIRE LANE WIDTH OF 20'. |
| | |
| | |
| | |
| | |
| | |
| |
Print |