2014-10-06 14:44:08THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESSES SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. ALL APARTMENT BUILDINGS SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE, 2010 EDITION, THE LIFE
 SAFETY CODE, 2009 EDITION, INCLUDING MORE SPECIFICALLY,
 CHAPTER 30, NEW APARTMENTS. THE DESIGNATION OF A
 TOWNHOME NOT REQUIRING THE ABOVE SHALL BE REVIEWED
 THROUGH FURTHER BUILDING DESIGN AND TENANT SEPARATIONS.
  
 6. THE CLUBHOUSE AND OTHER COMMON AREAS SHALL BE
 SUBJECT TO ANNUAL FIRE INSPECTIONS.
  
 7. AT THE CULBHOUSE, BASED ON ROOF DESIGN, NOTICE IS
 REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
 8. ALL UNDERGROUND FIRE LINE INSTALLATIONS TO FIRE
 HYDRANTS AND/OR FIRE SPRINKLER SYSTEMS SHALL BE
 SUBMITTED FOR PERMIT AND INSPECTED BY THE FIRE
 PREVENTION BUREAU'S FIRE INSPECTORS.
  
 9. FIRE HYDRANT LOCATIONS SHALL BE APPROVED IN PART
 THROUGH THE FIRE PREVENTION BUREAU AT A MINIMUM OF 300'
 SEPARATION.
  
 10. GATE ACCESS POINTS SHALL BE EQUIPPED WITH A KNOX
 KEY SWITCH FOR 24HR EMERGENCY ACCESS. THE GATE SHALL
 OPEN WITH A MINIMUM FIRE LANE WIDTH OF 20'.
  
  
  
  
  