2014-10-06 16:16:48THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. ALL APARTMENT BUILDINGS SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE, 2010 EDITION, THE LIFE
 SAFETY CODE, 2009 EDITION, INCLUDING MORE SPECIFICALLY,
 CHAPTER 30, NEW APARTMENTS.
  
 6. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR EACH
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED
 TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE
 PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 7. A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR EACH
 STRUCTURE. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 8. ALL VERTICAL AND HORIZONTAL FIRE SEPARATIONS FOR
 THIS BUILDING SHALL BE CLEARLY IDENTIFIED AND INDICATED
 ON THE PLANS.
  
 9. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL BE
 PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, DEAD-END CORRIDORS AND ALL FIRE SAFETY
 EQUIPMENT.
  
 10. REQUIRED FIRE SEPARATIONS BETWEEN EACH APARTMENT
 AND/OR TENANT SHALL BE CLEARLY INDICATED AND
 ILLUSTRATED ON THE BUILDING PLAN.
  
 11. REQUIRED CORRIDOR FIRE RATING SHALL BE CLEARLY
 INDICATED AND ILLUSTRATED ON THE BUILDING PLAN.
  
 12. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 13. ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 14. ALL FIRE WATER MAINS, SIZES AND THEIR VALVE
 ASSEMBLIES SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED
 ON THE PLAN.
  
 15. ANNUALLY, EMERGENCY INSTRUCTIONS ARE TO BE PROVIDED
 TO EACH APARTMENT AND/OR TENANT. THESE INSTRUCTIONS ARE
 TO INDICATE THE LOCATION OF ALARMS, EGRESS PATHS, AND
 ACTIONS TO BE TAKEN IN THE EVENT OF A FIRE OR ALARM
 ACTIVATION.
  
 16. NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
 17. 150?MAXIMUM ALLOWABLE DISTANCE FROM A FDC(FIRE
 DEPARTMENT CONNECTION) TO A FIRE HYDRANT. THE LOCATION
 OF THE FDC FOR EACH BUILDING SHALL BE COORDINATED
 THROUGHT THE BUREAU OF FIRE PREVENTION.
  
 18. NORMALLY HYDRANTS SHALL BE A MINIMUM DISTANCE OF 40
 FT. FROM A BUILDING. HYDRANTS CAN BE CLOSER THAN 40 FT.
 TO A BUILDING BASED UPON A REVIEW BY THE FIRE OFFICIAL.
  
 19 FIRE HYDRANT SPACING: 300? MINIMUM SEPARATION
 BETWEEN HYDRANTS IN A RESIDENTIAL NEIGHBORHOOD.
  
 20. 7.5? CLEARANCE IN FRONT AND TO THE SIDES
 (SEMI-CIRCLE) OF HYDRANTS, 4.5? BEHIND.
  
 21. ALL FIRE LINE FOR FIRE HYDRANTS AND/OR SPRINKLER
 SYSTMES SHALL BE PERMITTED AND INSPECTED BY A BUREA OF
 FIRE PREVENTION FIRE INSPECTOR.
  
 22. FOR THE REQUIRED FIRE LANE TURN-AROUND AT THE
 DEADEND PARKING LOT AREAS THE WIDTH SHALL BE 20'
 MINIMUM. (THE LOADING AREA)
  
  
  
  