Plan Review Notes
Plan Review Notes For Project Z14090015
Project Number Z14090015
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2014-10-06 12:12:12ENGINEERING/PUBLIC WORKS DEPT.
 LAND DEVELOPMENT AND STORMWATER
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION DETAILS
 WILL BE REVIEWED AS PART OF THE ENGINEERING DEVELOPMENT
 APPROVAL AND BUILDING PERMIT APPLICATION PROCESSES. THE
 ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS CAN
 BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL.
  
 1. REVISE THE PLANS TO INDICATE WHICH PORTIONS OF THE
 POTABLE WATER, SANITARY SEWER, AND STORMWATER SYSTEM
 WILL REMAIN PUBLICALLY OWNED AND WHICH SECTIONS WILL BE
 MAINTAINED BY THE APPLICANT. TYPICALLY, THE CITY'S
 OWNERSHIP STOPS AT THE RIGHT-OF-WAY LINE UNLESS
 EXTENUATING CIRCUMSTANCES REQUIRED THE OWNERSHIP
 DIVISION TO TAKE PLACE AT ANOTHER LOCATION.
  
 2. RELOCATE THE PROPOSED MASTER METER LOCATIONS TO
 WITHIN OR IMMEDIATELY ADJACENT TO THE DIVISION AVENUE
 RIGHT-OF-WAY.
  
 3. INDICATE THE LOCATIONS OF THE DUMPSTERS INTENDED TO
 BE SERVICE BY THE CITY OF WEST PALM BEACH SANITATION
 DEPARTMENT. DUMPSTERS MUST BE EASILY ACCESSIBLE BY THE
 CITY EQUIPMENT AND MANPOWER. (SECTION 74-35(A)(5) OF
 THE CODE OF ORDINANCES.)
  
 4. INCLUDE AN ESTIMATE OF THE SOLID WASTE YARDAGE
 ANTICIPATED TO BE GENERATED BY THE FACILITY AND VERIFY
 THAT THE ENCLOSURE SIZE IS LARGE ENOUGH TO ACCOMMODATE
 THE NEEDED DUMPSTER SIZE. THE DUMPSTER ENCLOSURES WILL
 NEED TO MEET THE REQUIREMENTS OF SECTION 94-444 OF THE
 CODE OF ORDINANCES AND INCLUDE CITY ENGINEERING DETAIL
 GC-8 ON THE CONSTRUCTION PLANS.
  
 5. PLEASE DEMONSTRATE THAT THE PROJECT WILL PROVIDE
 ADEQUATE DRAINAGE AND STORMWATER MANAGEMENT, INCLUDING
 NOT MODIFYING THE VELOCITY OR VOLUME OF OFF-SITE
 STORMWATER DISCHARGE. DESCRIBE HOW THIS WILL BE
 ACHIEVED. COMPLIANCE WITH CHAPTER 40E-4 WILL
 DEMONSTRATE COMPLIANCE WITH THIS PROVISION. THE DESIGN
 SHALL INCLUDE APPROPRIATE MEASURES SHALL BE TAKEN TO
 ENSURE THAT REMOVAL OF STORMWATER WILL NOT ADVERSELY
 AFFECT NEIGHBORING PROPERTIES OR THE PUBLIC STORM
 DRAINAGE SYSTEM. PROVISIONS SHALL BE MADE FOR THE
 CONSTRUCTION OF FACILITIES, INCLUDING GRADING, GUTTERS,
 PIPING AND THE TREATMENT OF TURF, TO ACCOMMODATE
 STORMWATER AND TO PREVENT EROSION AND THE FORMATION OF
 SILT. [SECTIONS 90-201, 94-35(C )(11), AND 94-307].
  
 6. PLEASE SHOW THE LOCATIONS OF THE ROOF DRAINS AND
 INDICATE WHERE THE RUNOFF FROM THE ROOF DRAINS WILL BE
 DIRECTED. THE ROOF DRAIN PEAK DISCHARGE RATE AND
 VELOCITY WILL NEED TO BE INCLUDED IN THE FINAL DESIGN
 OF THE STORMWATER MANAGEMENT SYSTEM.
  
 7. REVISE THE DRIVEWAY APRONS TO MEET THE CITY'S
 ENGINEERING DESIGN STANDARD GC-7.
  
 8. REVISE THE STRIPING DETAIL TO COMPLY WITH CITY OF
 WEST PALM BEACH CODE OF ORDINANCES, ARTICLE XV, SECTION
 94-485. (12 INCHES BETWEEN THE 4 INCH STRIPES RATHER
 THAN THE SHOWN 2 INCHES)
  
 9. INDICATE THE PROPOSED LOCATIONS OF THE STOP BARS AND
 STOP SIGNS.
  
 10. REVISE THE LANDSCAPE PLAN INCLUDE ROOT BARRIERS
 BETWEEN THE PROPOSED BUTTONWOOD TREES AND THE
 EXFILTRATION TRENCH.
  
 11. THE AVAILABLE WATER PRESSURE WITHIN THE CITY MAY
 NOT BE ACCEPTABLE AT ELEVATIONS HIGHER THAN THE 2ND
 FLOOR. WE RECOMMEND THAT A LONG-TERM PRESSURE STUDY BE
 PERFORMED ON THE POTABLE WATER LINES PRIOR TO
 FINALIZATION OF THE DESIGN.
  
 12. SECTION 78-9 OF THE CITY?S CODE OF ORDINANCES
 SPECIFIES NGVD 1929 AS THE OFFICIAL CITY VERTICAL
 DATUM. PLEASE REVISE THE PLANS AND SURVEY TO REFERENCE
 NGVD 29.
  
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 ENGINEERING & PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  