| Date |
Text |
| 2014-09-08 15:20:58 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM |
| | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE |
| | DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF |
| | POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. THE FIRE SPRINKLER AND FIRE ALARM SUBMITTAL APPEAR |
| | TO BE IN ORDER AND COMPLAINT. A MORE STRINGENT REVIEW |
| | WILL BE CONDUCTED AT THE TIME OF SUBMITTAL. |
| | |
| | 6. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS |
| | BUILDING. |
| | |
| | 7. COMPLETE LIFE SAFETY PLANS FOR THE BUILDING SHALL BE |
| | PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, EXITS, EXIT DISCHARGES, EMERGENCY LIGHTING, |
| | DEAD-END CORRIDORS AND ALL FIRE SAFETY EQUIPMENT. |
| | |
| | 8. OCCUPANT LOADS FOR ALL SPACES SHALL BE DETERMINED |
| | AND SUBMITTED WITH THE SUBMITTED PLAN AND WHEN APPROVED |
| | THEY ARE REQUIRED TO BE POSTED WHERE APPLICABLE. |
| | |
| |